background image

1

01

2017

ENGLISH

P

O

WER

 /

EN

ER

G

M

ETER

 SI

N

G

LE 

PH

A

SE

A

C

/D

C

 TR

M

R

S4

8

5

 M

O

D

B

U

S

Q

I-PO

WER

-4

8

5

-LV

POWER /ENERGY METER SINGLE PHASE

AC/DC TRMS - RS485 MODBUS

QI-POWER-485-LV

POWER SUPPLY

9...30 Vdc, protection against polarity reversal

and overtemperature.

 ABSORPTION

< 1,3  W

MEASUREMENT

Irms,  Vrms,  Watt,  Var,  Va,  Vpk,  Ipk,  Frequency,

Cosφ

, Energy bidirectional, THD, min e MAX of each measure

 TYPE OF MEASURE

TRMS or DC

 RANGE

Current: up to 50 A AC/DC
Voltage: up to 80 VAC or 100 VDC

 ACCURACY

 @25 °C up to 200 Hz

Voltage, Current,  Active Power:

< 0,5% F.S.

Frequency:

± 0,1 Hz

Energy:

± 1% of reading

Vpeak, Ipeak:

± 5% F.S.

 OUTPUT

RS485 Modbus RTU

 BAUDRATE

From 1.200 a 115.200 baud

 CREST FACTOR

1,8 (on current measurement)

 WORKING FREQUENCY

DC or 1...400 Hz

 SAMPLING RATE

11 k samples per second

 INPUT IMPEDENCE

1 Mohm ± 1%

 STANDARDS CE

EN61000-6-4/2006 + A1 2011;

EN64000-6-2/2005;  EN61010-1/2010

 OVERVOLTAGE CATEGORY

Cat IV up to 100 V

ISOLATION

3 kV on bare wire for Current measure.
4  kV  for  Voltage  measure  (reinforced  insulation  to  power  supply  and
serial output)

 PROTECTION INDEX

IP20

 TEMPERATURE COEFFICIENT

< 200 ppm/°C

WORKING TEMPERATURE

-15...+65°C

STORAGE TEMPERATURE

-40°C... +85°C

 HUMIDITY

10...90% not condensing

 ALTITUDE

Up to 2000 m s.l.m.

 DIMENSIONS

46,1 x 63 x 26,4 mm (terminal excluded)

 TERMINALS

Removable terminals 3,5 mm, n°1 of 4 poles, n°2 of

2 poles

 WEIGHT

80 g

 FILLING

Epoxy resin

 BOX MATERIAL

 PBT, grey

LED

N°1 yellow, power on fixed, data communication blinking

 DIP-SWITCH

2 poles

 MOUNTING

Screw  predisposition  for  vertical/horizontal  mounting,  DIN  rail  clips
(included) for vertical/horizontal mounting.

The

QI-POWER-485-LV

is  the

LOW  VOLTAGE

version  of  the

Single-phase  Power  meter

QI-POWER-485

, able to measure the RMS AC or DC

Current  and  Voltage.  On  the  RS485  Modbus  are
available:

Irms,  Vrms,  Watt,  VAR,  VA,  Vpk,  Ipk,

Frequency,  Cosφ,  Energy  bidirectional  and  THD

.

The device is fully

configurable by RS485

, DIN rail

mounting, 4kV galvanic isolation for Voltage input.

STRENGTHS:

LOW VOLTAGE VERSION;

TRMS Measure, THD available;

0,5 % Accuracy;

RS485 Modbus integrated;

Bidirectional energy metering;

DIN rail mounting in both side;

OEM’S design, low cost;

Fully  configurable  by  free  interface  software
FACILE QI-POWER-485;

Bootloader for updating firmware;

Available measure register: MSW first LSW first or
hundredts.

Reviews: