Installation and Operation Manual
Q
F
ire – Fire Brigade Switch
2.3.4
TURNING-OFF AUTOMATICALLY
2.3.4.1 CAUSED BY POWER GRID FAILURE
If the AC power is switched off, all relay voltages automatically drop and the relays open/interrupt the cir-
cuit.
The PV generator output is switched off. If the AC grid is turned back on, the Q
F
ire system automatically
switches the PV system back into operation.
2.3.4.2 CAUSED BY UNDERVOLTAGE
If there is a cable break within the control lines or if the control voltage drops below 9 VDC (e.g. in the case
of strong fluctuations in the AC network), this is detected as an undervoltage and the system is completely
switched off. The LED ERROR on the Q
Fire
control box lights up red.
Once the error has been resolved, the correct status display and the functioning of the system can be re-
stored by turning the S1 switch off and on again from 0 to 1.
3
DELIVERY CONTENT
3.1
UNPACKING
When unpacking, check that all supplied parts are complete and undamaged. Be sure to remove all parts from
the packaging. Claims for damages caused during transport can only be asserted if the delivery service is
notified immediately. Please prepare a damage report with appropriate photos and send it back to Q3 Energie
GmbH & Co. KG immediately with the defective part, see chapter 6.3 TECHNICAL SUPPORT, page 23.
The product is manufactured (customer specific), tested and packaged according to our strict quality stan-
dards. Each assembly has a serial number and is recorded in our QM system. Assemblies that are
connected to high voltages have been specially checked and a test report is enclosed. If there is any rea-
son for complaint, please have the serial number and test report available.
Damaged products must not be installed and put into operation under any circumstances!
There is a risk of malfunction, electric shock and fire!
Q3 Energie GmbH & Co. KG
Phone
+49 (0)8341/9080 334
IA-BA_QFire _E_AS002_V1.0
Moosmangstr. 8
Status
March 15, 2024
Page
16 | 28
87600 Kaufbeuren
Our general terms of business are to be applied.
Germany
Web
www.q3-energie.de
Errors and changes reserved.
eh
alten.