SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
817
■
n7-01 LoFreq Damping Gain
No.
(Hex.)
Name
Description
Default
(Range)
n7-01
(3111)
Expert
LoFreq Damping Gain
Sets the oscillation suppression gain for the low speed range.
1.0
(0.1 - 10.0)
Note:
•
If oscillation occurs in the low speed range, increase the acceleration time or increase the setting value in 0.5-unit increments.
•
To get starting torque with the setting for
C4-01 [Trq Comp Gain]
, decrease the setting value in 0.3-unit increments.
■
n7-05 TrqCtrl Response Gain
No.
(Hex.)
Name
Description
Default
(Range)
n7-05
(3115)
Expert
TrqCtrl Response Gain
Sets the response gain related to changes in the load.
1.00
(0.10 - 10.00)
Note:
To make tracking related to load changes better, increase the setting value in 5-unit increments. If oscillation occurs during load
changes, decrease the setting value in 5-unit increments.
■
n7-07 Speed Calc.Gain1
No.
(Hex.)
Name
Description
Default
(Range)
n7-07
(3117)
Expert
Speed Calc.Gain1
Sets the speed calculation gain during usual operation.
15.0 Hz
(1.0 - 50.0 Hz)
■
n7-08 Speed Calc.Gain2
No.
(Hex.)
Name
Description
Default
(Range)
n7-08
(3118)
Expert
Speed Calc.Gain2
Sets the speed calculation gain during a speed search.
25.0 Hz
(1.0 - 50.0 Hz)
Note:
When you increase the setting value, you can do a speed search of a motor rotating at a high frequency. If the setting value is too high,
the calculated speed will oscillate and a restart will fail. Decrease the setting value in these conditions.
■
n7-10 Pull-in SwitchSpeed
No.
(Hex.)
Name
Description
Default
(Range)
n7-10
(311A)
Expert
Pull-in SwitchSpeed
Sets a speed range proportional to the rated frequency that enables pull-in current commands.
Drive rated frequency = 100% value. If there is a large quantity of oscillation when you operate in
the low speed range, increase the setting value.
10.0%
(0.0 - 100.0%)
Note:
•
When the drive accelerates, it enables these settings:
–
Motor speed ≤
n7-10
+
n7-11 [DrvModeSwitchHysteresis Band]
:
n8-51 [Ac/Dec Pull-In Current]
–
Motor speed >
n7-10
+
n7-11
:
b8-01 [eSave Ctrl Selection]
•
When the drive decelerates, it enables these settings:
–
Motor speed ≤
n7-10
:
n8-51 [Ac/Dec Pull-In Current]
–
Motor speed >
n7-10
:
b8-01 [eSave Ctrl Selection]
•
If there is a large quantity of oscillation when you operate in the low speed range, increase the setting value.
•
When it is most important to save energy in the low speed range, decrease the setting value.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Summary of Contents for Q2A
Page 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Page 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Page 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...