SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
Note:
When Auto-Tuning changes the value of
E2-11 [Motor Rated Power (kW)]
, the drive will automatically set this parameter to the value
for a Yaskawa standard motor (4 poles). When you use a PM motor, the drive uses the value in
E5-01 [PM Mot Code Selection]
to
change this parameter.
Automatically Adjust Parameters
Execute the Inertia Tuning process when
A1-02 = 3 or 7 [Control Method = CLVector or PM CLVector]
.
Parameters are automatically adjusted.
Manually Adjust Parameters
Use this formula to find the motor acceleration time:
•
J
Motor
= Moment of inertia of motor (kg m
2
)
•
n
rated
= Motor rated speed (min
-1
, r/min)
•
T
rated
= Motor rated torque (N∙m)
The rated torque is calculated using the following expression.
P
Motor
= Motor Rated Power (kW)
■
L3-25 Load Inertia Ratio
No.
(Hex.)
Name
Description
Default
(Range)
L3-25
(046F)
Expert
Load Inertia Ratio
Sets the ratio between motor inertia and machine inertia.
1.0
(1.0 - 1000.0)
Set one of these parameters to enable
L3-25
:
•
L2-29 = 2 [KEB Method = Single KEB2 Ride-Thru]
•
L3-04 = 1 [StallP@Decel Enable = Enabled]
and
L3-50 = 1 [StallP@Decel Mode = Automatic Decel
Reduction]
•
L3-11 = 1 [Overvolt Supression Select = Enabled]
•
H1-xx = 42 or 43 [DI Function Select = KEB Thru2 NC or KEB Thru2 NO]
Note:
•
If you set this value incorrectly when
L2-29 = 1, H1-xx = 42 or 43
, or
L3-11 = 1
, it can cause large current ripples and
ov
[Overvoltage]
,
Uv1 [DC Bus Undervoltage]
, or
oC [Overcurrent]
faults.
•
KEB Tuning will automatically set this value.
Automatically Adjust Parameters
Do Inertia Tuning when
A1-02 = 3 or 7 [Control Method = CLVector or PM CLVector]
. The drive will
automatically adjust parameters.
Manually Adjust Parameters
Use this formula to find the load inertia ratio:
■
L3-26 DC Bus Capacitors Extension
No.
(Hex.)
Name
Description
Default
(Range)
L3-26
(0455)
Expert
DC Bus Capacitors
Extension
Sets the capacity for external main circuit capacitors. Sets this parameter when you use the KEB
Ride-Thru function. Usually it is not necessary to change this setting.
0 μF
(0 to 65000 μF)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Summary of Contents for Q2A
Page 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Page 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Page 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...