Note:
•
If you cannot operate the motor with the conditions in step 2 for the first test run and if the values set in
E2-02
and
E2-03
are much
different than data in the official test report for the motor and the data listed in
Defaults by Drive Model and Duty Rating ND/HD on
, these problems can occur:
–
Motor vibrations or hunting
–
Not sufficient torque
–
Overcurrent
In elevator applications, there is a risk of the cage falling and causing personal injury.
Do one of these precautions to decrease the risk:
–
After doing Stationary Auto-Tuning, operate the drive as specified by the conditions and procedure above.
–
Set
T1-12 = 0 [Test Mode Selection = No]
.
–
Do Rotational Auto-Tuning.
•
If you initialize the drive after completing Step 1, do the procedure beginning from Step 1 again.
•
For general-purpose motors, the target value for
E2-02
is 1 Hz to 3 Hz, and the target rated current for
E2-03
is 30% to 65%. Larger
capacity motors have a lower rated slip, and a smaller ratio for the no-load current rated current. Refer to
for details.
■
Precautions before Stationary Auto-Tuning for Line-to-Line Resistance and Stator
Resistance Auto-Tuning
In V/f control, when the motor cable is 50 meters (164 feet), do Stationary Auto-Tuning for Line-to-Line
Resistance.
WARNING!
Electrical Shock Hazard. In Stationary Auto-Tuning, the drive applies voltage to the motor. Do not touch the motor
until Auto-Tuning is complete. Failure to obey could cause serious injury.
■
Precautions before Inertia Tuning and ASR Tuning
Before Inertia Tuning or ASR Tuning, check these items:
WARNING!
Electrical Shock Hazard. In Rotational Auto-Tuning, the drive applies voltage to the motor before the motor rotates.
Do not touch the motor until Auto-Tuning is complete. Failure to obey could cause serious injury.
•
Do rotational motor parameter tuning or look at the motor test report or nameplate to enter the values manually.
•
Make sure that the motor magnetic brake is released.
•
Connect the motor and load.
•
Make sure that external force from the machine will not cause the motor to rotate.
•
Make sure that the machine does not prevent reverse rotation. You cannot do Inertia Tuning or ASR Tuning with
machines that prevent reverse rotation.
•
When the motor can rotate during Auto-Tuning, check for safety issues near the drive, motor, and machine.
Note:
If there are gears between the machine and motor shaft, Inertia Tuning or ASR Tuning are possibly not applicable.
■
Precautions before Using Deceleration Rate Tuning and KEB Tuning
Before Deceleration Rate Tuning or KEB Tuning, check these items:
Note:
•
Do not do Deceleration Rate Tuning if you use a braking resistor unit or a regenerative converter.
•
Do Deceleration Rate Tuning and KEB Tuning with the load attached to the motor.
•
Do not do Deceleration Rate Tuning or KEB Tuning for these applications:
In Deceleration Rate Tuning and KEB Tuning, the drive will automatically rotate the motor forward and accelerate and decelerate the
motor again and again.
–
On a machine that does not let the motor rotate forward
–
In applications with a small range of operation (trolleys and other such applications that can only move linearly)
–
In elevator applications
–
Applications where sudden acceleration and sudden deceleration are not applicable.
•
To do KEB Tuning with the external main circuit capacitors connected to the drive, set
L3-26 [DC Bus Capacitors Extension]
then do
KEB Tuning.
•
Do not do KEB Tuning or Deceleration Rate Tuning if the drive is set to use
H1-xx = 61 [H1-xx: MFDI Function Select = Motor 2
Select]
. Failure to obey can cause an
ov [Overvoltage]
fault.
◆
Auto-Tuning for Induction Motors
This section gives information about Auto-Tuning for induction motors. Set these parameters for Auto-Tuning:
•
Motor parameters
E1-xx [E1: V/F PARAMETER MOTOR 1], E2-xx [E2: MOTOR 1 PARAMETERS]
(
E3-xx
[E3: V/F PARAMETER MOTOR 2], E4-xx [E4: MOTOR 2 PARAMETERS]
for motor 2)
Summary of Contents for Q2A
Page 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Page 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Page 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...