background image

MAXIM• PACKAGED GAS/OIL WATER HEATER

NICKELSHIELD

®

  NICKEL-PLATED STORAGE TANK 

250 GALLON TANK SERIES 

 

MODEL NUMBER  

 

40-2.8 N 250A-PGO 

54-3.8 N 250A-PGO 

72-5.0 N 250A-PGO 

 

GPH Recovery at 40° to 120° F 

500 

670 

900 

 

GPH Recovery at 40° to 140° F 

400 

540 

720 

 Input 

Btu/h 

400,000 540,000 720,000 

 

Input, gph #2 Fuel Oil 

2.8 

3.8 

5.0 

Cold Inlet - NPT 

Hot Outlet - NPT 

Drain - NPT 

I - Beam Skids 

3 X 45 

3 X 45 

3 X 45 

Overall 

Height 

75 82 82 

Flue Outlet Diameter 

10 

Gas 

Inlet 

1 1 1 

 

Minimum Inlet Flow Gas Pressure 

4.5" W.C. 

4.5" W.C. 

6.5" W.C. 

 

Maximum Static Gas Pressure  

14" W.C. 

14" W.C. 

14" W.C. 

Oil 

Inlet 

1/2 1/2 1/2 

 

Motor HP  120 V, 1Ø, 60 Hz. 

1/3 

1/3 

1/2 

 Motor 

Amps 

10 

Height to Outlet 

65 

73 

73 

Height to Inlet 

28 

36 

36 

Overall 

Depth 

83 83 83 

Depth of Burner Housing 

31 

31 

31 

 

Approx. Shipping Weight - lbs 

1520 

1600 

1710 

Recoveries based on 83% thermal efficiency. ASHRAE 90.1 compliant. 
Dimensions are in inches unless otherwise specified. 
For standard and optional equipment, see form # PV 6679 

Product is patented in the U.S., Canada, and Mexico. 

 

PVI INDUSTRIES, LLC 

FORT WORTH, TEXAS 76111 

PV 6676  01/05

 

(800) 784-8326  

  www.pvi.com 

 

 

 

STANDARD ELECTRICAL REQUIREMENTS 

 

VENTING REQUIREMENTS 

CONTROL VOLTAGE

:  120V, 1Ø, 60 HZ., 2 AMPS 

MOTOR VOLTAGE

: 120V, 1Ø, 60 HZ. 

SEE ABOVE CHART FOR BLOWER MOTOR AMPS

 

 

-.02" TO -.06" W.C. (NEGATIVE PRESSURE). 

THE ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED 

UPON THE VENT CONNECTION DIAMETER EXCLUSIVELY. 

FOR PROPER VENT SIZING, CONSULT THE NATIONAL FUEL 

GAS CODE UNDER "FAN-ASSISTED".

1. Control Enclosure 
2. ASME Temperature & 
  Pressure Relief Valve 
3. 3” NPT Handhole 
4. Door swing requires 18" 
  in front of the water heater 

PVI RESERVES THE RIGHT TO CHANGE  

THE DESIGN AND SPECIFICATION WITHOUT NOTICE

 

 