![PVI Industries TURBOPOWER 1000 N 225A-TPO Specification Sheet Download Page 1](http://html1.mh-extra.com/html/pvi-industries/turbopower-1000-n-225a-tpo/turbopower-1000-n-225a-tpo_specification-sheet_1628912001.webp)
Recoveries based on 83% thermal efficiency. ASHRAE 90.1 compliant for efficiency and standby loss.
"J" dimension is for the burner housing only.
Dimensions are in inches unless otherwise specified.
For standard and optional equipment, see form PV 6004.
Model
Number
Recovery gph
Input
Btu/h
Gph
#2 Oil
Dimensions
(inches)
Blower
Motor
Shipping
Weight
lbs
40°- 120°F 40°- 140°F
A
B
J
HP
Volt/Ph/Amps
250 N 225A-TPO
250
200
199,000
1.4
28
4
17
1/3
115/1
∅
/8
1380
500 N 225A-TPO
500
400
399,000
2.8
28
5
17
1/2
115/1
∅
/10
1400
750 N 225A-TPO
750
600
600,000
4.3
42
6
17
1/2
115/1
∅
/10
1480
1000 N 225A-TPO
1000
800
800,000
5.7
42
8
17
1/2
115/1
∅
/10
1520
TURBOPOWER
®
OIL
PACKAGED WATER HEATER
NICKELSHIELD
®
NICKEL-PLATED STORAGE TANK
TANK SERIES 225 GALLONS
PV 5359 04/05
PVI INDUSTRIES, LLC
FORT WORTH, TEXAS 76111
(800) 784-8326
(817) 335-9531
www.pvi.com
Product is patented in the U.S., Canada, and Mexico.
VENTING REQUIREMENTS
-.02" TO -.06" W.C. (NEGATIVE PRESSURE)
ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED
UPON THE VENT CONNECTION DIAMETER EXCLUSIVELY.
FOR PROPER SIZING, CONSULT VENTING SUPPLIER.
STANDARD ELECTRICAL REQUIREMENTS
CONTROL VOLTAGE: 120V, 1Ø, 60 HZ., 2 AMPS.
MOTOR VOLTAGE:
208V, 230V, AND 460V MOTORS ARE AVAILABLE BUT WILL
REQUIRE A SEPARATE 120V/2 amps CONTROL CIRCUIT OR
AN OPTIONAL CONTROL CIRCUIT TRANSFORMER.
PVI RESERVES THE RIGHT TO CHANGE THE DESIGN
AND SPECIFICATION WITHOUT NOTICE.