PVI Industries TURBOPOWER 1000 N 225A-TPO Specification Sheet Download Page 1

  Recoveries based on 83% thermal efficiency.  ASHRAE 90.1 compliant for efficiency and standby loss. 
   "J" dimension is for the burner housing only.  

 

Dimensions are in inches unless otherwise specified. 

 

For standard and optional equipment, see form PV 6004.  

 

Model 

Number 

Recovery gph 

 

Input 

Btu/h 

Gph 

#2 Oil 

Dimensions 

(inches) 

Blower  

Motor 

Shipping 

Weight 

lbs  

40°- 120°F  40°- 140°F 

 

HP 

Volt/Ph/Amps 

250 N 225A-TPO 

250 

200 

199,000 

1.4 

28 

17 

1/3 

115/1

/8 

1380 

500 N 225A-TPO 

500 

400 

399,000 

2.8 

28 

17 

1/2 

115/1

/10 

1400 

750 N 225A-TPO 

750 

600 

600,000 

4.3 

42 

17 

1/2 

115/1

/10 

1480 

1000 N 225A-TPO 

1000 

800 

800,000 

5.7 

42 

17 

1/2 

115/1

/10 

1520 

TURBOPOWER

®

  OIL 

 

PACKAGED WATER HEATER 

NICKELSHIELD

®

 

NICKEL-PLATED STORAGE TANK

 

TANK SERIES 225 GALLONS  

PV 5359  04/05 

PVI INDUSTRIES, LLC 

FORT WORTH, TEXAS 76111 

(800) 784-8326 

 

(817) 335-9531 

 

www.pvi.com 

Product is patented in the U.S., Canada, and Mexico. 

VENTING REQUIREMENTS 

-.02" TO -.06" W.C. (NEGATIVE PRESSURE) 

 

ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED 

UPON THE VENT CONNECTION DIAMETER EXCLUSIVELY.  

FOR PROPER SIZING, CONSULT VENTING SUPPLIER. 

STANDARD ELECTRICAL REQUIREMENTS 

CONTROL VOLTAGE: 120V, 1Ø, 60 HZ., 2 AMPS. 
  MOTOR VOLTAGE:  
  208V, 230V, AND 460V MOTORS ARE AVAILABLE BUT WILL 
  REQUIRE A SEPARATE 120V/2 amps CONTROL CIRCUIT OR 
  AN OPTIONAL CONTROL CIRCUIT TRANSFORMER. 

PVI RESERVES THE RIGHT TO CHANGE THE DESIGN 

AND SPECIFICATION WITHOUT NOTICE. 

Reviews: