PVI Industries MAXIM 20 N 125A-MXS Specifications Download Page 1

Product is patented in the U.S., Canada, and Mexico. 

 

PVI INDUSTRIES, LLC 

FORT WORTH, TEXAS 76111 

PV 6139  08/07

 

(800) 784-8326  

  www.pvi.com 

MAXIM • PACKAGED GAS WATER HEATER

 

NICKELSHIELD

®

  NICKEL-PLATED STORAGE TANK 

125 GALLON TANK SERIES 

 

MODEL NUMBER 

20 N 125A-MXS

27 N 125A-MXS

40 N 125A-MXS

54 N 125A-MXG  72 N 125A-MXG

80 N 125A-MXG

 

GPH Recovery at 40° to 120° F 

245 

330 

490 

670 

900 

1000 

 

GPH Recovery at 40° to 140° F 

195 

260 

390 

540 

720 

800 

 

Input 

Btu/h 

199,000 270,000 399,000 540,000 720,000 800,000 

Min. inlet flow gas pressure " W.C. 

5.5 

5.5 

5.5 

4.5 

4.5 

4.5 

Max static gas pressure “W.C. 

14 

14 

14 

A  Cold Inlet - NPT 

B  Hot Outlet - NPT 

Drain 

NPT 

1 1 1 1 1 1 

D  I - Beam Skids 

3 x 34-1/2 

3 x 34-1/2 

3 x 34-1/2 

3 x 34-1/2 

3 x 34-1/2 

3 x 34-1/2 

Overall 

Depth 

45 45 45 53 52 54 

Overall 

Height 

75 75 75 82 82 82 

G  Flue Outlet Diameter 

10 

10 

H  Gas Inlet - NPT 

1/2 

3/4 

3/4 

1-1/4 

1-1/4 

J  Motor HP  120 V, 1Ø, 60 Hz. 

1/6 

1/6 

1/6 

1/3 

1/3 

1/3 

K Motor 

Amps 

1.75 

1.75 

1.75 

Height 

to 

Outlet 

65 65 65 73 73 73 

Height 

to 

Inlet 

28 28 28 36 36 36 

 

Approx. Shipping Weight - lbs 

1020 

1070 

1130 

1260 

1370 

1390 

ASHRAE 90.1 compliant. 
Models with suffix “MXS” are registered as low NOx water heaters in California and Texas 
*  The information presented is for natural gas 0.6 S.G. – For operation with propane (LP gas), consult the factory. 
*  For gas pressures outside of this range, consult factory. 
Dimensions are in inches unless otherwise specified. 
For standard and optional equipment, see form # PV 6137. 

 

 

 
 

 

STANDARD ELECTRICAL CONNECTIONS 

 

VENTING REQUIREMENTS 

CONTROL VOLTAGE: 120V, 1Ø, 60 Hz, 2 amps 

SEE ABOVE CHART FOR BLOWER MOTOR AMPS 

 

-.02

"

 TO -.06

"

 W.C. (negative pressure) 

TYPE B VENTING 

THE ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED 

UPON THE

 

VENT CONNECTION DIAMETER EXCLUSIVELY. 

FOR PROPER VENT SIZING, CONSULT THE NATIONAL FUEL 

GAS CODE UNDER “FAN-ASSISTED”

 

 
 
 

PVI RESERVES THE RIGHT TO CHANGE THE DESIGN AND 
SPECIFICATION WITHOUT NOTICE. 

 

1. Control Enclosure 
2. ASME Temperature & 
  Pressure Relief Valve 
3. 3” NPT Handhole

Reviews: