DeltaTherm IR Cure Module
Revision B
/
February 2020
Page 24 of 41
Setup Mode
In Setup mode, the operator can set basic functions of the machine and Auto Cycle
parameters. These parameters (depending on the machine) are the current recipe, IR panel
temperatures, allowable deviations, conveyor width, and conveyor speed. Parameters are
saved in the controller under the current recipe even when the module is shut down. Push
the Home button or the F3 button at any time to exit Setup mode and return to cycle stop.
IR Panels
Figure 18: Setup Zone 1 Panels
1.
The
Heater Panel Recipe Switch
can disable or enable the use of a zone’s upper or
lower heater panel in Autocycle. If enabled, the panel will display a
green
checkmark
. If disabled, the panel will display a
red X
.
Note: IR panels cannot activate unless the exhaust fan is on.
2.
The
Setpoint
box is the target temperature (display temperature is filtered) for
each zone and the deviation box is the permitted deviation from the setpoint for
that zone.
•
Touch the Setpoint box and a keypad will be shown.
•
Enter the necessary value. The system minimum and maximum are shown
below the numeric field.
•
Press “
ENT
” to save the value and close the keypad.