76
Settings
Touch the Edit icon to view or change the settings related to the relay.
Alarm Mode
Select the alarm conditions that will put the relay into the alarm state:
All Alarms
Selected Alarms
On Delay Time
Enter the delay time for relay activation in hours:minutes:seconds. Set the time
to 00:00:00 to immediately activate the relay.
Off Delay Time
Enter the delay time for relay deactivation in hours:minutes:seconds. Set the
time to 00:00:00 to immediately deactivate the relay.
Select Alarms
Scroll through the list of all inputs and outputs, as well as System Alarms and
Network (Ethernet) alarms. Touch the parameter to select alarms related to that
parameter, then scroll through the list of alarms. Touch each alarm to check the
box indicating the alarm is selected. Touch the Confirm icon when finished with
that parameter to save the changes.
Repeat for each input and output.
Output
Select if the relay will be active when in the alarm state (Normally Open) or if
the relay will be active when not in the alarm state (Normally Closed).
5.3.9
Relay or Control Outputs, Time Proportional Control Mode
Output Details
The details for this type of output include the relay on/off state, HOA mode or Interlock status, the current % on
time calculated for the cycle, the current point in the cycle time, accumulated on-time, alarms related to this output,
current cycle on time, relay type and the current control mode setting.
Settings
Touch the Edit icon to view or change the settings related to the relay.
Set point
Enter the sensor process value at which the relay will be off for the entire Sample Period.
Proportional Band
Enter the distance that the sensor process value is away from the set point at which the
relay will be on for the entire Sample Period.
Sample Period
Enter the duration of the sample period.
Input
Select the sensor to be used by this relay.
Direction
Select the control direction.
Daily Max Time
Enter the maximum amount of accumulated on-time, in Hand or Auto modes, that the
relay can have between midnight and midnight the next day. If the time is exceeded,
the relay will deactivate, and a Daily Max Timeout alarm will be triggered. The alarm
will clear, and relay allowed to reactivate at midnight the next day.
If the relay was in Hand mode when the alarm was triggered, it will revert to
whichever HOA state it was in prior to being set to Hand.
To override the Daily Max Limit for the rest of the day, press Reset Output
Timeout.
5.3.10
Relay or Control Outputs, Intermittent Sampling Control Mode
ONLY AVAILABLE IF HVAC MODES ARE ENABLED IN CONFIG MENU – GLOBAL SETTINGS
In an Intermittent Sampling with Proportional Blowdown control mode, the controller reads an analog input on
a timed schedule, and the relay responds to maintain the conductivity value at the set point by activating for a
programmable amount of time that varies with the deviation from the set point.