126
REPLACE ELECTRODES
Occurs if the user has set an Electrode Alarm and the number of days selected since the last time “Replace Corrosion Electrode” has
been confirmed has passed.
Possible Cause
Corrective Action
The Electrode Alarm timer has expired
Replace the electrodes and then confirm in the Replace Corrosion
Electrode menu
WiFi MODULE FAILURE
The WiFi module is not responding
Possible Cause
Corrective Action
WiFi board not connected properly
Power down, reseat WiFi board, power up
Faulty WiFi board
Replace WiFi board
WiFi CONNECTION ERROR
The WiFi module is unable to connect to the specified Infrastructure access point
Possible Cause
Corrective Action
Missing settings
WiFi Status will be “Invalid Config”. Enter the missing settings.
Incorrect settings
Check with the LAN admin for the correct settings
Invalid key
WiFi Status will be “Invalid Key”. Check with the LAN admin for
the correct settings.
Poor signal
WiFi status will be “Network Not Found” or “Unable to Connect”.
Improve signal.
Access point is not working
WiFi status will be “Network Not Found” or “Unable to Connect”.
Have LAN admin check access point functionality.
Faulty WiFi board
Replace WiFi board
UPDATE TIMEOUT
This alarm occurs if a Remote Modbus Input does not receive the requested data within the programmed Timeout Alarm Delay time
Possible Cause
Corrective action
No Ethernet connection to the Modbus application
Check wiring
Invalid Modbus communications settings
Check settings
Timeout Alarm Delay time is too short
Increase delay time
MESSAGE ERROR
This alarm occurs if the Remote Modbus Input receives an error message from the Modbus application instead of the requested data
Possible Cause
Corrective action
Invalid Modbus communications settings
Check settings. Enable Verbose Logging to see the exact error.
BOOLEAN ALARM
This alarm occurs if a Boolean Logic output is in the state in which it is programmed to alarm.
Possible Cause
Corrective action
Improperly programmed
Program correctly
Normal operation
Respond to the cause of the relay being in the alarm state
DAILY MAX TIMEOUT
This alarm occurs if an output has been activated for longer than the programmed Daily Max Time Limit.
Possible Cause
Corrective Action
Improperly programmed
Program correctly
Normal operation
Respond to the cause of the relay being activated for too long
8.3 Procedure for Evaluation of Conductivity Electrode
Try cleaning the electrode first (refer to Sect. 7.1). To check the electrode, check the electrode connections to the
terminal strip (refer to Figure 7). Make sure that the correct colors go to the correct terminals, and that the connections
are tight. Restore power and see if the conductivity is back to normal. If not, replace the electrode.