ULTRATWIN (UL)
INSTRUCTION MANUAL
132
Control
P*210, 220, 230, 240, 250, 260 = 3 (Control)
When a relay is being set as a
control
relay, the second parameter that will
be displayed in the menu determines its
function
.
P*211, P221, P231, 241, 251, 261 - Relay Function,
This function allows the relay to be assigned to specific control functions
(other than pumps and alarms) several of these functions work in relation to
time.
This can be used to activate devices based on elapsed time or running
cycles, such as a timed rake control to keep a ram lubricated if idle for long
periods, or flush valve operation.
OPTIONS
DESCRIPTION
0 = Off (Default)
Relay is always de-energised
1 = Time
Relay will
energise
“
ON
” after the
Cycle time
that is set in
Relay
Setpoint 2
(P*2
1
4, 2
2
4, 2
3
4). And turns “
OFF
”,
de-
energises
, after the
On-Time Period
that is set in Relay
Setpoint 1
(P*2
1
3, 2
2
3, 2
3
3, 2
4
3, 2
5
3)
5 = Step Time
Step Time Control allows relays to be used to control a
device, such as a motorised valve or gate, in order to
maintain the level within two predetermined points. Relays
will
energise
“
ON
” when Step Time condition is in effect and
de-energises
“
OFF
” when S
tep Time goes off. One relay will
be required to control an increase in level, (‘open’ the device)
and a second relay is required to control a decrease in level,
(‘close’ the device).
Alarm ID
(P*2
1
2, 2
2
2, 2
3
2, 2
4
2, 2
5
2, 2
6
2)
is used to assign the relay to control either the
open
or
close
condition. Step Time Control relay requires three setpoints.
The first set point (P*2
1
3, 2
2
3, 2
3
3, 2
4
3, 2
5
3, 2
6
3) determines
the
level
, at which the relay is to be activated, (N.B. level
setpoint for
open
relay,
increase
the level, must be
lower
than
the setpoint for the
close
relay,
decrease
the level). The
relay will
energise
“
ON
” after the
Limit time
that is set in
Relay
Setpoint 3
(P*2
1
5, 2
2
5, 2
3
5, 2
4
5, 2
5
5, 2
6
5). And turns
“
OFF
”,
de-energises
, after the
Drive Period
that is set in
Relay
Setpoint 2
(P*2
1
4, 2
2
4, 2
3
4, 2
4
4, 2
5
4, 2
6
4).