PULSAR MEASUREMENT
11
About the UltraTWIN
UltraTWIN has two independent points of measurement, the wall mount
model provides a dedicated display to each point of measurement, whilst
the fascia model, whilst in RUN, will show detail of one point of
measurement in the main display line, with the second point being displayed
on the auxiliary display line. In both models, the display will provide
information relevant to the point of measurement selected whilst in
RUN
and
PROGRAM
mode
UltraTWIN combines premium specification with high performance in a most
versatile system which is quickly configurable offering a choice of
applications in any combination, between the two points of measurement of
three specific applications i.e., level or volume measurement, pump control
or flow measurement.
Functional Description
UltraTWIN sends a transmit pulse to the transducer(s), which emits an
ultrasonic pulse perpendicular to the transducer face, and the returned echo
is sent back to the UltraTWIN. The time taken to receive the echo is
measured and the distance from the transducer face to the surface being
monitored is calculated.
UltraTWIN can measure from zero to 40m from the transducer to the surface
being monitored, dependent on the application chosen and transducer
used.
Six user-definable relays can be programmed to activate alarms, pump
starters, or other control equipment, and can be allocated to either point of
measurement. Also provided are four user definable digital inputs on the
wall mount model and seven on the fascia mount model, which can be
allocated to either point of measurement.