www.pulsar.pl
PSBEN2024C
BLACK POWER
32
W
H
D
Additional accessories
(not included)
- USB-
TTL ‘INTU’ interface; USB-TTL communication
-
RS485 ‘INTR’ interface: RS485 communication
- USB-
RS485 ‘INTUR’ interface; USB-RS485 communication
-
Ethernet ‘INTE’ interface; Ethernet communication
-
WiFi “INTW’ interface; Wi-Fi wireless communication
- RS485-
Ethernet “INTRE’ interface; RS485-Ethernet
communication
- RS485-
WiFi “INTRW’ interface; RS485-WiFi wireless
communication:
Table 14. Mechanical parameters.
Enclosure dimensions
400 x 350 x 98 (WxHxD) [mm] (+/- 2)
Mounting
See Fig. 3
Battery space
2x17Ah/12V (SLA) max.
380 x 165 x 85mm (WxHxD) max
Net/gross weight
5,9/6,4 kg
Enclosure
Steel plate DC01 1mm, color RAL 9005 (black)
Closing
Cheese head screw x2 (at the front), lock assembly possible
Terminals
Supply:
Φ0,63÷2,50 (AWG 22-10)
Outputs : Ф0,51÷2 (AWG 24-12), BAT battery outputs: 6,3F-2,5, 30cm
Notes
The enclosure does not adjoin the assembly surface so that cables can be led.
Convectional cooling.
Table 15. Safety of use.
Protection class
EN 60950-1:2007
I (
first
)
Protection grade
EN 60529: 2002 (U)
IP20
Insulation electrical strength:
- between input (network) circuit and the output circuits of the PSU (I/P-O/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit (O/P-FG)
3000 V/AC min.
1500 V/AC min.
500 V/AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500V/DC