Features of the power supply unit:
•
power output 5A/12
÷
15VDC
•
universal AC input voltage range 85÷264V
•
high efficiency 80%
•
LED optical signalisation
•
protections:
•
SCP short-circuit protection
•
overvoltage OVP
•
overvoltage protection (AC input)
•
overload (OLP)
1. Technical description.
1.1. General description.
The power supply unit is intended for the feeding of alarm system equipments, which require 12V DC supply
voltage and current load I=5A. The design enables simple changing of the output voltage, within the range of 12V÷15V
DC, using a potentiometer. The power supply unit is protected against short-circuit, overload and overvoltage.
1.2. Technical parameters.
Supply voltage
85 ÷ 264 V AC, 120 ÷ 370 V DC
Current consumption
0,6A@230VAC max.
Supply power
60W max.
Efficiency
80%
Output voltage
12V DC
Output current
5A
Output current t
AMB
<30°C
5A - see graph 1.
Output current t
AMB
=40°C
3,5 A - see graph 1.
Voltage adjustment range
12 V ÷ 15V DC
Ripple voltage
100mV p-p max.
Short-circuit protection SCP
electronic, automatic recovery
Overload protection OLP
105-150% of power supply, automatic recovery
Overvoltage protection OVP
U>115% ÷ 135% of the output, isolation
of the output voltage, automatic recovery
Optical signalisation
green LED – presence of DC voltage
Operation conditions
2-nd enviromental class, temperature: -10
o
C÷40
o
C
relative humidity 20%...90%, without condensation
Dimensions (LxWxH)
159 x 97 x 38 [mm]
Net/gross weight
0,48kg / 0,51kg
Protection class PN-EN 60950-1:2007
I (first) – requires a protective conductor (PE)
Connectors
power-supply:
Φ
0,63-2,50 (AWG 22-10)
outputs :
Φ
0,63-2,50 (AWG 22-10)
Electrical strength of insulation:
- between input (network) circuit and output circuits of
power-supply (I/PO/P)
- between input circuit and PE protection circuit (I/P-
FG)
- between output circuit and PE protection circuit
(O/P-FG)
3000 V/AC min.
1500 V/AC min.
500 V/AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 M
Ω
, 500V/DC
Storage temperature
-20ºC...+60ºC
Vibrations and impulse waves during transport
according to PN-83/T-42106