Pulsar MSR 1012 Manual Download Page 1

 

 

MSR 1012

 

v.1.0 

MSR 13,8V/1A

 

Buffer, switch mode power supply module 

with technical output FAC. 

EN** 

Edition: 2 from 11.05.2015 

Supersedes the edition: 1 from 18.09.2014 

 

 

 
 

 
 

 
 

 

 

 
 
 
 

 
 
 

           

 
 
 

 
 

 

 
 

 
 
 

Summary of Contents for MSR 1012

Page 1: ...MSR 1012 v 1 0 MSR 13 8V 1A Buffer switch mode power supply module with technical output FAC EN Edition 2 from 11 05 2015 Supersedes the edition 1 from 18 09 2014 ...

Page 2: ...scription of components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 LED indication 3 2 Technical outputs 4 Operation and use 4 1 Overload or short circuit of the PSU module output 4 2 Battery assisted operation 4 3 Maintenance 1 Technical description 1 1 General description A buffer PSU module is intended for an uni...

Page 3: ...DC supply output AUX U AUX GND FAC AC absence technical output relay type CAUTION In Fig 2 the contact set in the potential free status corresponds to a state with no AC power AC power failure 4 LEDs optical indication AC AC voltage LB battery charge AUX output voltage DC 5 Connector to the external LED indicators AC and AUX 6 IBAT jumper battery charging current selection IBAT Ibat 0 2A IBAT Ibat...

Page 4: ...rox 10s FBAT fuse F2A 250V Mechanical parameters tab 4 Enclosure dimensions 85 x 58 x 25 WxLxH mm 2 Fixation Dowel pins x4 PCB fi 4 2 mm Net gross weight 0 07kg 0 12kg Connectors Outputs Ф0 41 1 63 AWG 26 14 Battery output BAT 6 3F 2 5 30cm Operating parameters tab 5 Environmental class II Operating temperature 10ºC 40ºC Storage temperature 20ºC 60ºC Relative humidity 20 90 without condensation Vi...

Page 5: ...230V AC power to the transformer the AC diode and the AUX diode should be permanently illuminated 10 Check the output voltage the PSU voltage without load should amount to 13 6V 13 9V during battery charging 11V 13 8V If the value of the voltage requires adjustment it should be set by the VADJ potentiometer monitoring the voltage at the AUX output of the PSU module 11 Check the current consumption...

Page 6: ...T in the battery circuit becomes permanently damaged and the restoration of the voltage at the BAT output requires the replacement of the fuse 4 2 Battery assisted operation In case of a main power outage the device is immediately switched into a battery assisted operation The PSU module is not equipped with a discharged battery disconnection system 4 3 Maintenance Any and all maintenance operatio...

Page 7: ...period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried out at the service centre of the manufacturer exclusively 8 The warranty does not cover the defects of the equipment result...

Page 8: ...www pulsar pl MSR1012 8 Pulsar Siedlec 150 32 744 Łapczyca Poland Tel 48 14 610 19 40 Fax 48 14 610 19 50 e mail biuro pulsar pl sales pulsar pl http www pulsar pl www zasilacze pl ...