Parameter Listing
This section describes all of the parameters. Any parameter can be reset to
its default, by pressing the
hot key, whilst in program mode.
Application Parameters
Operation
P102 Mag Threshold
This parameter sets the sensitivity of FlowPulse sensor. The Mag Threshold
value sets the required level of signal above the minimum signal before the
FlowPulse decides it is seeing flow. The default is set at 1600 which means
that the FlowPulse must see a signal strength of at least 16 above the
minimum signal before it decides there is flow.
Default = 1600
P104 Damping
This parameter sets the damping of the FlowPulse unit. The value of the
damping sets the amount of flow readings it uses to create an average flow.
The default is set to 24, meaning the average of 24 readings will be used as
the flow value.
Default = 24
P105 Averaging
This is the number of averaging to perform on the reading – this is
independent of the damping process.
Reducing this will increase flow sampling rate at the expense of
measurement stability.
Default = 6
P108 Cal Factor
This parameter sets the calibration factor for the FlowPulse unit in
percentage. The FlowPulse is designed to give a repeatable flow value.
However, if the value being read by the FlowPulse does not meet the flow
value that is expected the Cal Factor can be used to modify the output.
Default = 100
%
P110 Pipe Diameter
This parameter sets the internal pipe diameter of the pipe that the FlowPulse
is connected to.
Default = 0.1 metre
Summary of Contents for Flow Monitor
Page 1: ...Flow Monitor INSTRUCTION MANUAL...
Page 2: ......
Page 4: ......
Page 10: ...Page 4 EU Declaration of Conformity...
Page 17: ...Page 11 Your Flow Monitor can be programmed directly via the integral keypad...
Page 26: ...Page 20 This page left blank intentionally...
Page 61: ...Page 55...