www.pulsar.pl EN54C-LCD
RED POWER plus
5
1. PSU features.
Compliant with requirements of
EN 54-4:2001+A1:2004+ A2:2007
EN 12101-10:2007+AC:2007 standards
and pt. 12.2 of Regulation of Minister of Interior
and Administration of Republic of Poland of
27.04.2010
27,6 V DC uninterruptible power supply
available versions with
2 A / 3 A / 5 A / 10 A
current efficiencies
available versions with space for
7 Ah
– 65 Ah
batteries
independently protected outputs AUX1 and
AUX2
high efficiency (up to 89%)
low level of voltage ripple
microprocessor-based automation system
measurement of resistance of battery circuit
automatic temperature-compensated charging
automatic battery test
two-stage battery charging process
accelerated battery charging
monitoring of continuity of battery circuit
monitoring of battery voltage
monitoring of charging and maintenance of
batteries
deep discharge battery protection (UVP)
battery overcharge protection
LoB low battery voltage indication
battery output protection against short-circuit
and reverse connection
output voltage control
fuse monitoring of AUX1 and AUX2 outputs
„SERIAL” communication port with
implemented MODBUS RTU protocol and
TCP/IP
– a list of registers is available
cooperation with EN54C-LB4 and EN54C-LB8
fuse modules (optional equipment)
cooperation with EN54C-LS4 and EN54C-LS8
sequential modules (optional equipment)
relay output of collective failure ALARM
EPS relay output indicating 230 V power loss
EXTi input of external failure
protections:
o
SCP short-circuit protection
o
OLP overload protection
o
OVP overvoltage protection
o
surge protection
o
antisabotage protection
– Tamper
closing enclosure
– lock
convection cooling (forced only in
EN54C-10AxxLCD)
Warranty
– 3 years from production date
MOREOVER, IN THE VERSION WITH A LCD
AND ETHERNET COMMUNICATION
optical indication
– LCD display
o
display of electrical parameters, e.g.
voltage, current, resistance of battery circuit
readings
o
failure indication
o
PSU settings adjusted from panel’s level
o
adjustable delay for 230 V AC power loss
indication
o
2 levels of password protected access
o
operation memory of PSU
o
failure memory
o
a real-time clock (RTC) with battery backup
remote monitoring
o
Ethernet communication or RS485 (option)
o
embedded PowerSecurity web application
o
preview of the operating parameters:
voltages, currents, temperature and
resistance of the battery circuit
o
PSU work history chart from a period of
more than 100 days: voltages, currents and
resistance of the battery circuit
o
battery operating temperature readings
from period up to 5 years
o
event log of up to 2048 power supply
failures
o
SSL email encryption
o
remote battery test