
www.pulsar.pl EN54C-LCD
RED POWER plus
23
Table 6. Description of screen symbols - current parameters of PSU.
Screen field
Description
Additional
information
– ~230 V power ON
(highlighted = present mains supply 230 V)
see section 8.2.2
– indication power at AUX1 output
(highlighted = present voltage at AUX1 output)
– indication power at AUX2 output
(highlighted = present voltage at AUX2 output)
– indicates battery failure
(highlighted = battery failure)
sections:
7.4.5
5.1
– Signal of a collective failure of the PSU
(highlighted = failure)
sections:
7.4.5
5.1
Current electrical parameters of PSU:
U
aux1
– AUX1 output voltage
U
aux2
– AUX2 output voltage
U
bat
– battery voltage
I
ld
– battery charging current
I
bat
– battery discharge current
R
bat
– resistance of battery circuit
T
bat
– battery temperature
sections:
7.4.2
Status of technical outputs:
EPS
– indicating presence of AC voltage
open = AC power failure
closed = AC power
– O.K.
ALARM
– sygnalizacja awarii zbiorczej
CAUTION!
Set of contacts shows a potential-free status of
relay, which corresponds to power supply failure.
EXTi
– EXTi input status indication
(highlighted = EXTi input activated)
TAMPER
–
Status of TAMPER input
(highlighted = input activated)
sections:
7.4.5
5.1
7.4.3. LCD screen
– current failures
In case of abnormal electrical parameters during operation, PSU will indicate a failure by displaying a message
on LCD, turning on red LED on panel, activating acoustic indication (if enabled) and changing status of a dedicated
technical output..
Fig. 18. Message indicating blown fuse at AUX1 output.
At a given time, multiple failures can occur. To check which faults are indicated, choose current failures of PSU
screen.
To do that, press „ESC” button, use „<” or „>” buttons to choose
icon and press „SET” button to confirm