EN54-7A40LCD
RED POWER
47
Table 17. Safety of use.
Protection class EN 60950-1:2007
I (first)
Protection grade EN 60529: 2003
IP42
Insulation electrical strength:
- between input (network) circuit and the output circuits of the PSU
- between input circuit and protection circuit
- between output circuit and protection circuit
3000 V AC min.
1500 V AC min.
500 V AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500 V DC
Table 18. Operation parameters.
Environmental class EN 12101-10:2007
2
Operating temperature
-5
ºC...+75 ºC
Storing temperature
-25
ºC...+60 ºC
Relative humidity
20 %...90 %, no condensation
Sinusoidal vibrations during operation:
10
÷ 50 Hz
50
÷ 150 Hz
0,1 G
0,5 G
Surges during operation
0,5 J
Direct insolation
unacceptable
Vibrations and surges during transport
According to the PN-83/T-42106 standard
Table 19. Recommended types and sections of installation cables.
Mains supply ~230 V L-N-PE
(see Table 2 [2])
OMY 3 x 0,75 mm
2
…1,5 mm
2
AUX1, AUX2 output terminals
(see Table 1 [11])
HLGs 2 x 1,5 mm
2
…2,5 mm
2
Indication inputs/outputs
(see Table 1 [11])
YnTKSY 1 x 2 x 0,8 mm
2
Additional indication lines (with optional interface)
FTP 4x2x0,5 cat. 5e