www.pulsar.pl
DSOP24V
46
SCP
replacement
Under-voltage protection (UVP).
U<20V (± 2%) – disconnection (+BAT) of the batteries
Technical outputs:
- EPS; output indicating AC power failure
- APS; output indicating battery failure
- PSU; output indicating PSU failure
- ALARM; output indicating collective failure
- Type
– relay
EXTi technical input
Normal operation (no failure): opened
Failure- electrical contacts are closed
Ethernet communication
10Base-T/100Base-TX
Optical indication
- Output voltage readings
- Output current readings
- Resistance of the battery circuit readings
- Mains supply voltage readings
- Failure codes with history
Acoustic indication:
- Piezoelectric indicator ~75dB /0.3m
Fuses:
- OUT1...OUT9
- ROUTER
- CONTROLLER
- BATTERY
F 30A / 250V/ 6,3x32mm
F 6.3A / 250V/ 5x20mm
F 10A / 250V/ 6,3x32mm
T 100A
1)
/ 250V, 22x58mm
Mounting dimensions:
W=19”, H=2U
1)
Depending on the DSO configuration.
2)
Full range of operating temperatures, taking into account accelerated charging and discharged batteries during
battery operation
3)
Permissible only during battery operation.
Table 18. Safety of Use.
Protection class PN-EN 60950-1:2007
I (first)
Protection grade PN-EN 60529: 2003
IP30
Insulation electrical strength:
- between the input (network) circuit and the output circuits of the PSU (I/P-O/P)
- between the input circuit and PE protection circuit (I/P-FG)
- between the output circuit and PE protection circuit (O/P-FG)
3000 V/AC min.
1500 V/AC min.
500 V/AC min.
Insulation resistance:
- between input, output, and protective circuit
100 MΩ, 500V/DC
Table 19. Operation parameters.
Environmental class PN-EN 12101-10:2007
1
Operation temperature
-
5ºC...+40ºC
Storage temperature
-
25ºC...+60ºC
Relative humidity
20%...90%, no condensation
Sinusoidal vibrations during operation:
10
÷ 50Hz
50
÷ 150Hz
0,1g
0,5g
Surges during operation
0,5J
Direct insolation
unacceptable
Vibrations and surges during transport
According to the PN-83/T-42106 standard