PULSAR MEASUREMENT
41
P102 Material
This parameter should be set to the type of material being monitored.
OPTION
DESCRIPTION
1 = Liquid (Default)
Used for liquids and flat solid materials.
2 = Solid
Used for sold material that is heaped or at an angle.
3 = Closed Tank
Use for applications within a closed tank or where a
secondary echo response may become focused to
create a larger echo than the first.
Distance
P104 Measurement Units
This parameter sets the units you want to use for programming and display.
OPTION
DESCRIPTION
1 = metres (Default)
All units of measurement are
Metres
2 = cm
All units of measurement are
Centimetres
3 = mm
All units of measurement are
Millimetres
4 = feet
All units of measurement are
Feet
5 = inches
All units of measurement are
Inches
P105 Empty Level
This parameter is to be set to the maximum distance from the face of the
transducer to the empty point, in
P104
Measurement
Units
. Note this value
affects span as well, so should be set before span.
Default: dBi-M3 = 3.00m
(9.84 feet), dBi-M6 = 6.00m (19.69 feet), dBi-M10 = 10.00m (32.81 feet)
and
dBi-M15 = 15.00m (49.21 feet)
.
P106 Span
This parameter should be set to the maximum distance from the
Empty
Level
(
P105
) to the maximum material level. It must be set at least to be
equal to the
Empty
Level
(
P105
) less the
Near
Blanking
distance (
P107
)
when you set the empty level.
Default dBi-M3 = 2.80m (9.19 feet), dBi-
M6 = 5.70m (18.70 feet),
dBi-M10 = 9.70m (31.82 feet)
and
dBi-M15 =
14.5m (47.57)