PULSAR MEASUREMENT
51
LOE Save Trace
P950 Save DATEM Trace on LOE
When enabled this parameter will ensure that in the event of the unit going
into a LOE situation a trace at the time of the LOE occurrence is saved for
future reference.
OPTION
DESCRIPTION
0 = Off
Feature is disabled and in the event of LOE
echo trace will NOT be saved.
1 = Enable (Single Trace)
In the event of a LOE situation an echo trace
WILL be saved and stored for future reference.
Once a LOE trace has been saved no further
traces will be taken
2 = Enable Overwrite
(Default)
In the event of an LOE event occurring any
previous trace will be overwritten and the last
LOE trace saved.
DATEM
P020 Set DATEM
This parameter allows DATEM to be reset to its default value. To reset
DATEM to its default value set parameter value to 1, the trace will then be
set to its default value and then update as normal.
P021 Set Dist.
Allows the user or service personnel to determine which echo is to be
displayed. On start-up, if the unit displays an incorrect reading then simply
enter the distance from the transducer to the required level and, if an echo is
present at this point, the Gate will establish itself around the chosen echo,
DATEM will update in front of the Gate and reference out any other
unwanted echoes.
It should be noted that DATEM will reset to default values whilst performing
this function, and reform itself once it has selected an echo.
Enter distance from
the face of transducer to the target
in units of
measurement P104
Values: Min. 0.000, Max. 99.00