background image

 

                                         

                                        

Short operating manual for maintenance-free batteries  

                                               (VRLA)

                              

                                                     

- ACUMAX

® 

of the AML series 

                                                       - ALARMTEC of the BP series 

                                 - the FGB series 

 

 

                                                                                                                                                                                                                  

Edition: 1 from 01.12.2014  

                                                                                  Supersedes the edition: ----------

 

    

                                                                                                                                  

                                 

EN*

 

1. Safety:

 

 

Always  follow  the  manufacturer's  instructions  and  safety  instructions.  The  battery  should  only  be  operated  by  qualified 
persons with appropriate permissions. 
 
-  Due  to  the  risk  of  explosion  or  fire,  no  smoking,  open  fire  and  sources  of  ignition  are  allowed  in  the  room  where  the 
battery pack (cells) is installed. 
 

-  Hydrogen  in  the  air  can  produce  an  explosive  mixture.  Therefore,  proper  air  exchange  (natural  ventilation  - 
gravity or forced) in the place of use of the batteries (cells) should be ensured. 
 

- When operating the batteries,  wear  protective clothing and goggles! Be sure to follow accident prevention the rules of 
and DIN VDE 0510 and VDE 0105 Part 1. 
 
- In case of contact of acid with skin, wash the burn with water and seek medical help. Stains on clothing should be rinsed 
with water. 
 
- There  is  a  risk  of fire  and  explosion  and  short  circuits  should  be  avoided.  Metal  parts  of  the  battery  are  always  under 
voltage; neither instruments nor tools should be placed on them. 
 
-  There  is  a  risk  of  electric  shock.  Batteries  (cells)  accumulate  a  large  amount  of  energy  electricity  and  even  when 
discharged can force the flow of short circuit current. It is necessary to prevent the possible short circuits of positive (+) 
and negative (-) terminals (poles) of a single battery (cell) or the whole battery pack (batteries consisting of multiple cells 
can  have  a  voltage  dangerous  to life).  Before  operating  the  batteries,  remove  all  jewelry  and  metal  ornaments  and  use 
only insulated tools. 
 
- The electrolyte is highly corrosive. Under normal operating conditions there is virtually no possibility of contact with the 
electrolyte.  The  electrolyte  may  leak  through  the  safety  valves  in  case  of  overcharging  or  mechanical  damage  to  the 
container. In case of contact with the electrolyte, immediately rinse the place with plenty of water. 
 
-  The  batteries  (cells)  are  very  heavy.  Therefore,  both  suitable  fastening  equipment  and  transport  equipment  should  be 
provided. 
 

In  case  of  failure  to  comply  with  the  instruction  manual,  repairs  using  non-original  parts  or  other  prohibited 
actions (e.g. opening valves) - the warranty will be void. 

  

2. Recycling:

  

 

The relevant provisions on the disposal of hazardous waste should be applied. The batteries (cells) marked with the 
disposal symbol should be delivered to recycling facilities or - if so agreed - returned to the manufacturer. Used batteries 
must not be mixed with chemical or household waste. 

 

 

3. Operating parameters:

  

 

 
a) Charging: 
 

Maintenance-free batteries must be charged using constant voltage limiting initial charging current (IU characteristic). The 
initial  charging  current  should  not  exceed 

0.3  C  [A]

  (C-  battery  capacity)  that  is,  for  example, 

8.4  [A]

  for  the 

EP  28-12

 

model. The recommended initial charging current is 

0.1 

of the battery capacity, that is 

2.8 [A]

 for the EP 28-12 model. 

 
 
 