Application Parameters
Operation
P100 Mode of Operation
This parameter sets the mode of operation, when in run mode, and can be
set to one of the following:
OPTION
DESCRIPTION
When Ultra Wizard = 1 Level/Volume, 2 Pump or 3 Flow
1 = Distance (Default)
Display shows the distance from the transducer face
to the surface of the material measured.
2 = Level
Shows how full a vessel is.
3 = Space
Shows how empty a vessel is.
When Ultra Wizard = 1 Level/Volume
5 = Volume
Display shows volume of the vessel
When Ultra Wizard = 3 Flow
4 = OCM Head
Display shows how high the head is.
5 = OCM Flow
Display shows the instantaneous flow
P
101 Xducer (Transducer)
This parameter should be set to the transducer being used with the unit, and
can be set to one of the following:
OPTION
DESCRIPTION
When Ultra Wizard = 1 Level/Volume, 2 Pump
1 = dB3
Transducer is a dB3. Range = 0 to 3 metres
2 = dB6 (default)
Transducer is a dB6. Range = 0.3 to 6 metres
3 = dB10
Transducer is a dB10. Range = 0.3 to 10 metres
4 = dB15
Transducer is a dB15. Range = 0.5 to 15 metres
7 = dBS6
Transducer is a dBS6. Range = 0.2 to 6 metres
8 = dBMach3
Transducer is a dBMach3. Range 0.3 to 1.50 metres
When Ultra Wizard = 1 Level/Volume
5 = dB25
Transducer is a dB25. Range 0.60 to 25 metres
6 = dB40
Transducer is a dB40. Range 1.2 to 40 metres
OPTION
DESCRIPTION
Summary of Contents for Ultra 3
Page 1: ...Ultra 3 Instruction Manual...
Page 14: ...ULTRA 3 INSTRUCTION MANUAL 14 EU Certificate of Conformity...
Page 18: ...ULTRA 3 INSTRUCTION MANUAL 18 The full dimensions of the enclosure are as shown below...
Page 22: ...ULTRA 3 INSTRUCTION MANUAL 22 Dimensions of the panel enclosure are as shown below...