3.2 Location
Select a mounting location convenient to grounded electrical and plumbing
connections. It is recommended that you mount the controller on a wall or other vertical
surface with adequate lighting at a comfortable level. A mounting-hole template is
supplied with your controller. Installation should comply with all national, state, and local
codes.
A
VOID LOCATIONS WHERE THE CONTROLLER WOULD BE SUBJECTED TO EXTREME COLD
OR HEAT
{
LESS THAN
0°F
(-17,8°C)
OR GREATER THAN
122°F
(50°C)},
DIRECT
SUNLIGHT
,
VIBRATION
,
VAPORS
,
LIQUID SPILLS
,
OR
EMI
(
ELECTROMAGNET
INTERFERENCE
;
E
.
G
.,
STRONG RADIO TRANSMISSION AND ELECTRIC MOTORS
.)
S
AFETY PROTECTION PROVIDED BY THE EQUIPMENT MAY BE IMPARED IF THE
EQUIPMENT IS USED IN A MANNER NOT SPECIFIED BY THE MANUFACTURER
.
T
HIS
CONTROLLER IS INTENDED FOR INDOOR USE ONLY
.
MOUNTING HOLES
.17 in. (4,4 mm) DIA.
MOUNTING HOLES
.17 in. (4,4 mm) DIA.
BLEED
INHIB
BIO A
BIO B
SUPPLY
BLEED
INHIB
BIO A
BIO B
5A
F2
5A
F1
HOT
RET
HOT
RET
H
OT
R
ET
H
OT
R
ET
H
OT
R
ET
H
OT
R
ET
PL2
PL3
PL4
PL5
HOT
no
nc
Fig.
3
Mount the bottom half of the controller using the four (4) holes provided
(Fig. 3
).
3.3 Mounting Hardware
For panel mounts without threaded inserts, four number 8 self taping screws are the
minimum recommendation.
For panel mounts with threaded inserts, four 8-32 screws are the minimum