background image

 

 

PIC480.241C, PIC480.241C-C1 

 

 

 

 PIANO-Series

 

 

24V,

 

20A,

 

480W,

 

S

INGLE 

P

HASE 

I

NPUT

 

 

 

Mar. 2021 / Rev. 1.2 DS-PIC480.241C-EN 
All parameters are typical values specified at 24V, 20A output, 230Vac input , 25°C ambient and after a 5 minutes run-in time 

unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278 0    Germany 

8/19 

 

9.

 

E

FFICIENCY AND 

P

OWER 

L

OSSES

 

 
Efficiency  

typ. 

95.7% 

at 24V, 20A, 230Vac 

Average efficiency

*)

 

typ. 

95.2% 

25% at 5A, 25% at 10A, 25% at 15A. 25% at 20A 

Power losses 

typ. 

1.35W 

at 24V, 0A, 230Vac 

 

typ. 

10.7W 

at 24V, 10A, 230Vac 

 

typ. 

21.6W 

at 24V, 20A, 230Vac 

*)   The average efficiency is an assumption for a typical application, where the power supply is loaded with 25% of the nominal load for 

25% of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 

100% of the nominal load for the rest of the time. 

 

 

Fig. 9-1

   Efficiency vs. output current at 24V, 

typ. 

 

Fig. 9-2

   Losses vs. output current at 24V, typ.  

 

Efficiency

4

93

95

96

91

97%

20A

8

14 16

12

Output Current

18

10

6

94

92

 

 

Power Losses

0

4

8

16 18 20A

0

4

12

16

24W

8

12

20

14

10

6

2

Output Current

 

 

 

 

10.

 

L

IFETIME 

E

XPECTANCY AND 

MTBF 

 
Lifetime expectancy

*)

 

93 000h 

at 24V, 10A and 40°C, 230Vac 

 

264 000h

*)

 

at 24V, 10A and 25°C, 230Vac 

 

51 000h 

at 24V, 20A and 40°C, 230Vac 

 

144 000h

*)

 

at 24V, 20A and 25°C, 230Vac 

MTBF

**)

  SN 29500, IEC 61709 

482 000h 

at 24V, 20A and 40°C, 230Vac 

 

894 000h 

at 24V, 20A and 25°C, 230Vac 

MTBF

**)

  MIL HDBK 217F 

207 000h 

at 24V, 20A and 40°C, 230Vac; 
Ground Benign GB40 

 

279 000h 

at 24V, 20A and 25°C, 230Vac; 
Ground Benign GB25 

 

45 000h 

at 24V, 20A and 40°C, 230Vac; 
Ground Fixed GF40 

 

57 000h 

at 24V, 20A and 25°C, 230Vac; 
Ground Fixed GF25 

*)   The 

Lifetime expectancy

 shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime 

expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the 

capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years 
(131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices. 

**) 

MTBF

 stands for 

M

ean 

T

ime 

B

etween 

F

ailure, which is calculated according to statistical device failures, and indicates reliability of a 

device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product. 

 

The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that 

statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit 

has been running for 50 000h or only for 100h. 

Summary of Contents for PIANO Series

Page 1: ...tiple mains inputs the reduction to a regional input voltage range AC 200 240V simplifies the circuitry and has significant advantages for reliability efficiency and cost The addition of a DC OK signa...

Page 2: ...is document is correct to the best of our knowledge and experience at the time of publication If not expressly agreed otherwise this information does not represent a warranty in the legal sense of the...

Page 3: ...t by following all local and national codes Use appropriate copper cables that are designed for a minimum operating temperature of 60 C for ambient temperatures up to 45 C 75 C for ambient temperature...

Page 4: ...99 at 24V 20A 230Vac see Fig 3 4 Crest factor typ 1 6 at 24V 20A 230Vac Start up delay typ 400ms see Fig 3 2 Rise time typ 60ms at 24V 20A const current load 0mF load capacitance see Fig 3 2 typ 240m...

Page 5: ...INPUT INRUSH CURRENT A NTC inrush limiter which is bypassed by a relay contact during normal operation limits the input inrush current after turn on of the input voltage Inrush current max 32Apeak 40...

Page 6: ...tage 13 5Vdc see Fig 6 1 Short circuit current min 21A load impedance 50mOhm see Fig 6 1 max 25A load impedance 50mOhm see Fig 6 1 typ 8 1A average R M S current load impedance 50mOhm see Fig 6 1 Outp...

Page 7: ...90 230Vac Input Voltage 50 60 Hold up Time 70 a b c d a 24V 10A typ b 24V 10A min c 24V 20A typ d 24V 20A min 5 Hold up Time Zero Transition Output Voltage Input Voltage 8 DC OK RELAY CONTACT This fea...

Page 8: ...and 25 C 230Vac MTBF SN 29500 IEC 61709 482 000h at 24V 20A and 40 C 230Vac 894 000h at 24V 20A and 25 C 230Vac MTBF MIL HDBK 217F 207 000h at 24V 20A and 40 C 230Vac Ground Benign GB40 279 000h at 24...

Page 9: ...ructed and suitable for field and factory wiring Input and output DC OK Signal Type Screw terminals Push in terminals Solid wire max 6mm2 max 1 5mm2 Stranded wire max 4mm2 max 1 5mm2 American Wire Gau...

Page 10: ...wer com Phone 49 89 9278 0 Germany 10 19 13 FRONT SIDE AND USER ELEMENTS Fig 13 1 Front side A Input Terminals screw terminals N L Line input PE Protective Earth input B Output Terminals screw termina...

Page 11: ...200Vac 140Vac 50 of 200Vac 100Vac 1000ms 500ms 200ms Criterion A Criterion C Criterion C Powerful transients VDE 0160 over entire load range 750V 0 3ms Criterion A Criterions A Power supply shows norm...

Page 12: ...to 6000m 6 560 to 20 000ft reduce output power or ambient temperature see Fig 15 2 IEC 62103 EN 50178 overvoltage category II Altitude de rating 30W 1000m or 5 C 1000m 2000m 6500ft see Fig 15 2 Over...

Page 13: ...s down and automatically attempts to restart Class of protection I According to IEC 61140 A PE Protective Earth connection is required Ingress protection IP 20 According to EN IEC 60529 Over temperatu...

Page 14: ...ucting the test When testing set the cut off current settings to the value in the table below Fig 17 1 Dielectric strength A B C D A D C B B N L Input DC ok Earth PE Output Type test 60s 2500Vac 3000V...

Page 15: ...eclaration Online Document Airborne Contaminants Corrosion Test Severity Level G3 Harsh H2S 100ppb NOx 1250ppb Cl2 20ppb SO2 300ppb Test Duration 3 weeks which simulates a service life of at least 10...

Page 16: ...ICAL DIMENSIONS AND WEIGHT Width 49mm 1 93 Height 124mm 4 88 Depth 124mm 4 88 The DIN rail height must be added to the unit depth to calculate the total required installation depth Weight 620g 1 37lb...

Page 17: ...dancy module which can be used to build 1 1 and N 1 redundant systems It is equipped with two input channels which can be connected to power supplies with up to 10A output current and one output which...

Page 18: ...breaker should be used 22 3 PARALLEL USE TO INCREASE OUTPUT POWER Do not use the power supply in parallel to increase the output power 22 4 PARALLEL USE FOR 1 1 REDUNDANCY Power supplies can be parall...

Page 19: ...ng capacitive and inductive loads If extreme large capacitors such as EDLCs electric double layer capacitors or UltraCaps with a capacitance larger than 1 5F are connected to the output the unit might...

Reviews: