![Puls MiniLine-2 ML30.241 Manual Download Page 21](http://html1.mh-extra.com/html/puls/miniline-2-ml30-241/miniline-2-ml30-241_manual_1624301021.webp)
ML30.241
MiniLine-2
24V,
1.3A,
S
INGLE
P
HASE
I
NPUT
2
40V
+10%
max.
Fuse
L2
L1
L3
L
N
PE
Power Supply
AC
DC
internal
fuse
22.9.
O
PERATION ON
T
WO
P
HASES
The power supply can also be used on two-phases of a three-phase-system. A
phase-to-phase connection is allowed as long as the supplying voltage is
below 240V
+10%
. Use a fuse or a circuit breaker to protect the N input. The N
input is not internally protected and is in this case connected to a hot wire.
Appropriate fuses or circuit breakers are specified in section 22.4.
22.10.
U
SE
W
ITHOUT
PE
ON THE
I
NPUT
From a safety standpoint, the unit is internally designed according to the requirements for Protection Class 1 and 2.
Please contact PULS if you do not plan to use the PE terminal. A different marking of the front foil is then required.
Grounding of the input is beneficial for a high EMI immunity: Symmetrical spikes or fast transients on the input side
can be conducted directly to earth by the built-in filter capacitors. The magnitude of such spikes or fast transients on
the output side caused by the input is much smaller compared to not connecting this terminal to ground.
Fig. 22-3
Earthed input
Fig. 22-4
Not earthed input
Surge
Y
X
L
N
Ground
Power Supply
+
-
Surge
X
L
N
Power Supply
+
-
24V
Spike
Mar. 2013 / Rev. 1.2 DS-ML30.241-EN
All parameters are specified at 24V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
21/23