QTD20.241
Q-Series
24V,
20A,
DC
I
NPUT
8.
E
FFICIENCY AND
P
OWER
L
OSSES
DC 600V
Efficiency
typ.
95.0%
At 24V, 20A
Average efficiency
*)
typ.
94.4%
25% at 5A, 25% at 10A, 25% at 15A and 25% at 20A
Power losses
typ.
7.7W
At 24V, 0A (no load)
typ.
12.8W
At 24V, 10A (half load)
typ.
25.5W
At 24V, 20A (full load)
*) The average efficiency is an assumption for a typical application where the DC/DC converter is loaded with 25% of the nominal load for
25% of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with
100% of the nominal load for the rest of the time.
Fig. 8-1
Efficiency vs. output current at 24V,
typ.
Fig. 8-2
Losses vs. output current at 24V, typ.
Efficiency
4
6
8
10
12
14
16
18 20A
88
89
90
91
92
93
94
95
96%
Output Current
Power Losses
0
2
4
6
8 10 12 14
20A
0
5
10
15
20
25
30W
16 18
Output Current
Fig. 8-3
Efficiency vs. input voltage at 24V,
20A, typ.
Fig. 8-4
Losses vs. input voltage at 24V, 20A,
typ.
Efficiency
350
450
650
750
850Vdc
92.5
93.0
93.5
94.0
94.5
95.0
95.5%
Input Voltage
550
Power Losses
350
450
550
650
850Vdc
23.0
25.0
27.0
29.0
31.0
33.0
35W
750
Input Voltage
Oct. 2016 / Rev. 2.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
9/27