QTD20.241
Q-Series
24V,
20A,
DC
I
NPUT
5.
O
UTPUT
Output voltage
nom.
24V
Adjustment range
min.
24-28V
Guaranteed
max.
30V
3)
At clockwise end position of potentiometer
Factory setting
typ.
24.1V
±0.2%, at full load, cold unit
Line regulation
max.
10mV
At 480-840Vdc voltage change
Load regulation
max.
100mV
Static value, 0A
Æ
20A
Ripple and noise voltage
max.
100mVpp
20Hz to 20MHz, 50Ohm
Output current – continuous nom.
20A
4)
At 24V, input: 480-840Vdc, see Fig. 5-1
nom.
17.5A
4)
At 28V, input: 480-840Vdc, see Fig. 5-1
Output current – up to 4s
1)
nom.
25A
At 24V, input: 480-840Vdc, see Fig. 5-1 and Fig. 5-3
nom.
21.4A
At 28V, input: 480-840Vdc, see Fig. 5-1 and Fig. 5-3
Output power – continuous
nom.
480W
At 24-28V
Output power – up to 4s
1)
nom.
600W
At
24-28V
BonusPower
®
time typ.
4s Duration
until
the output voltage dips, see Fig. 5-3
BonusPower
®
recovery time
typ.
7s
Overload free time to reset power manager, see Fig.
5-4
Overload behavior
cont. current
Short-circuit current
2)
min.
20A
Continuous,
load impedance 50mOhm, see Fig. 5-1
max.
23A
load impedance 50mOhm, see Fig. 5-1
min.
25A
Short-term
(4s),
load impedance 50mOhm, see Fig. 5-1
max.
28A
Short-term (4s), load impedance 50mOhm, see Fig. 5-1
Output capacitance
typ.
950μF
Included in the DC/DC converter
1)
BonusPower
®
, short term power capability (up to typ. 4s)
The DC/DC converter is designed to support loads with a higher short-term power requirement without damage or shutdown. The
short-term duration is hardware controlled by an output power manager. This BonusPower
®
is repeatedly available. Detailed
information can be found in chapter 21.1. If the DC/DC converter is loaded longer with the BonusPower
®
than shown in the bonus-
time diagram (see Fig. 5-3), the max. output power is automatically reduced to 480W.
2)
Discharge current of output capacitors is not included.
3)
This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not
guaranteed value which can be achieved. The typical value is about 28.5V.
4)
Reduce output current according to Fig. 5-2 for the extended input voltage ranges from 360-480Vdc and 840-900Vdc.
Oct. 2016 / Rev. 2.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany