17.
D
IELECTRIC
S
TRENGTH
The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by the manufacturer.
Field tests may be conducted in the field using the appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s
down). Connect all input-terminals together as well as all output poles before conducting the test. When testing, set the cut-off current
settings to the value in the table below.
Fig. 17-1
Dielectric strength
A
B
C
A
C
L
Input
Earth, PE
Output
+
-
N
B
Type test
60s
2500Vac
3000Vac
500Vac
Factory test
5s
2500Vac
2500Vac
500Vac
Field test
5s
2000Vac
2000Vac
500Vac
Cut-off current setting
> 15mA
> 15mA
> 20mA
To fulfil the PELV requirements according to EN60204-1 § 6.4.1, we
recommend that either the + pole, the
–
pole or any other part of the
output circuit shall be connected to the protective earth system. This helps
to avoid situations in which a load starts unexpectedly or can not be
switched off when unnoticed earth faults occur.