CS10.241, CS10.241-S1
CS-Series
24V,
10A,
240W
S
INGLE
P
HASE
I
NPUT
Aug. 2022 / Rev. 2.1 DS-CS10.241-EN
All parameters are specified at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
3/27
1.
I
NTENDED
U
SE
This device is designed for installation in an enclosure and is intended for commercial use, such as in industrial control, process control,
monitoring, measurement equipment or the like.
Do not use this device in equipment, where malfunctioning may cause severe personal injury or threaten human life without additional
appropriate safety devices, that are suited for the end-application.
If this device is used in a manner outside of its specification, the protection provided by the device may be impaired.
Without additional measures to reduce the harmonic input current (PFC), the power supply is not suited to be connected to the public
mains system in residential, commercial and light-industrial environments. No additional measures are necessary for use in industrial
environments. Exceptions for various countries outside the European Union exist and can be determined locally.
2.
I
NSTALLATION
I
NSTRUCTIONS
WARNING
Risk of electrical shock, fire, personal injury or death.
- Turn power off before working on the device and protect against inadvertent re-powering.
- Do not open, modify or repair the device.
- Use caution to prevent any foreign objects from entering into the housing.
- Do not use in wet locations or in areas where moisture or condensation can be expected.
- Do not touch during power-on, and immediately after power-off. Hot surface may cause burns.
Obey the following installation instructions:
This device may only be installed and put into operation by qualified personnel.
This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect.
If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to the factory for
inspection.
Install device in an enclosure providing protection against electrical, mechanical and fire hazards.
Install the device onto a DIN rail according to EN 60715 with the input terminals on the bottom of the device. Other mounting
orientations require a reduction in output current.
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper cables that are designed for a
minimum operating temperature of 60°C for ambient temperatures up to +45°C, 75°C for ambient temperatures up to +60°C and 90°C
for ambient temperatures up to +70°C.
Ensure that all strands of a stranded wire enter the terminal connection. Use ferrules for wires on the input terminals. Unused screw
terminals should be securely tightened.
The device is designed for pollution degree 2 areas in controlled environments. No condensation or frost is allowed.
The enclosure of the device provides a degree of protection of IP20.The housing does not provide protection against spilled liquids.
The device is designed for overvoltage category II zones. Below 2000m altitude the device is tested for impulse withstand voltages up to
4kV, which corresponds to OVC III according to IEC 60664-1.
The device is desig
ned as “Class of Protection I” e
quipment according to IEC 61140. Do not use without a proper PE (Protective Earth)
connection.
The device is suitable to be supplied from TN, TT and IT mains networks. The continuous voltage between the input terminals and the PE
potential must not exceed 300Vac.
A disconnecting means shall be provided for the input of the device.
The device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not cover ventilation
grid!