Aug. 2022 / Rev. 2.1 DS-CS10.241-EN
All parameters are specified at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
26/27
22.10.
O
PERATION ON
T
WO
P
HASES
The power supply can also be used on two-phases of a three-phase-system. A phase-to-phase connection is allowed as long as the
supplying voltage is below 240V
+10%
.
22.11.
U
SE IN A
T
IGHTLY
S
EALED
E
NCLOSURE
When the power supply is installed in a tightly sealed enclosure, the temperature inside
the enclosure will be higher than outside. In such situations, the inside temperature defines the ambient temperature for the power
supply.
The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure.
The power supply is placed in the middle of the box, no other heat producing items are inside the box
Enclosure:
Rittal Typ IP66 Box PK 9519 100, plastic, 180x180x165mm
Load:
24V, 8A; (=80%) load is placed outside the box
Input:
230Vac
Temperature inside enclosure:
48.9°C (in the middle of the right side of the power supply with a distance of 2cm)
Temperature outside enclosure:
23.3°C
Temperature rise:
25.6K
240V
+
1
0
%
m
ax
.
Fuse
L2
L1
L3
L
N
PE
Power Supply
AC
DC
internal
fuse