CS10.241, CS10.241-S1
CS-Series
24V,
10A,
240W
S
INGLE
P
HASE
I
NPUT
Aug. 2022 / Rev. 2.1 DS-CS10.241-EN
All parameters are specified at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
10/27
8.
E
FFICIENCY AND
P
OWER
L
OSSES
AC 100V
AC 120V
AC 230V
Efficiency
typ.
90.7%
91.0%
91.6%
at 24V, 10A
typ.
90.0%
90.7%
91.2%
at 24V, 12A (PowerBoost)
Average efficiency
*)
typ.
90.5%
90.2%
91.0%
25% at 2.5A, 25% at 5A,
25% at 7.5A. 25% at 10A
Power losses
typ.
5.8W
8.4W
7.5W
at 24V, 0A
typ.
12.0W
12.3W
11.3W
at 24V, 5A
typ.
24.6W
23.7W
22.0W
at 24V, 10A
typ.
31.9W
29.6W
27.9W
at 24V, 12A (PowerBoost)
*)
The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25% of the time, 50% of
the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100% of the nominal load for the rest of the
time.
Fig. 8-1
Efficiency vs. output current at 24V, typ
Fig. 8-2
Losses vs. output current at 24V, typ.
Efficiency
2
89
90
91
88
92%
12A
4
8
10
Output Current
6
(a)
(b)
(c)
(a) 100Vac
(b) 120Vac
(c) 230Vac
Power Losses
0
2
4
8
10
12A
0
4
12
16
24
28
32W
8
6
20
(a)
(b)
(c)
(a) 100Vac
(b) 120Vac
(c) 230Vac
(a) (b)(c)
Output Current
Fig. 8-3
Efficiency vs. input voltage at 24V, 10A, typ.
Fig. 8-4
Losses vs. input voltage at 24V, 10A, typ.
Efficiency
85
120
155
190
225 260Vac
88
89
90
Input Voltage
91
92%
Power Losses
9
12
15
18
21
24
27W
85
120
155
190
225 260Vac
Input Voltage