PT113
Instruction Manual
56
9.5 PT113CO – CANopen
After setting related parameters (address in the Gatway tab of AzComT 6.3.4.4 or with the
programming switch 5.1.3), communication with the indicator via a CANopen network is possible.
9.5.1.1 EDS File
A sample EDS file is provided to assist with PLC interfacing. This should be tailored by the PLC
programmer to suit the specific application.
9.5.1.2 CANopen Interface
The interface is described in 5.1.2.6. In summary it has automatically detected and supported baud
rates of 10 kbps, 50 kbps, 100 kbps, 125 kbps, 250 kbps, 500 kbps, 800 kbps, 1 Mbps and Autobaud
(default).
There are 2 LED’s near the CANopen connector which are Error and Run above and below the
CANopen connector respectively, with meanings as below.
Run LED
State
Indication
Comment
Off
Not online / No power
Check power and cable
Green
On-line, data exchange
-
Green, blinking
On-line, initializing
-
Green, single flash
Stopped
Check hardware for damage
Green, flickering
Auto baudrate detection in progress
-
Red
CANopen configuration error
Check EDS file
Error LED
State
Indication
Comment
Off
-
No power or CANopen module is in
initialization state
Red, single flash
Warning limit reached
A bus error counter reached or
exceeded its warning level
Red, flickering
LSS
LSS services in progress
Red, double flash
Error count event
A guard- (NMT-Slave or NMT-
master) or heartbeat event
(Heartbeat consumer) has occurred.
Red
Bus off (Fatal Event)
Bus off.
EDS Configuration
The CANopen data structures of the PT113CO includes 3 x TxPDO (32 bit) and 3 x RxPDO (32 bit).
EDS configuration for PLC programmers is shown in below.
Figure 12.4
- EDS Configuration
EDS Configuration
Description
TxPDO 1 (T_DW1, 2 words)
TxPDO 2 (T_DW2, 2 words)
TxPDO 3 (T_DW3, 2 words)
Dword (PT113
CO Output to PLC Input
)
RxPDO 1 (R_DW1, 2 words)
RxPDO 2 (R_DW2, 2 words)
RxPDO 3 (R_DW3, 2 words)
Dword (
PLC Output to PT113CO Input
)