---------- PROXEL ENGINEERING ---------------- www.proxel-bg.com-------------------------------- 3WMREG rev. 2.4 /02.2017------      
 

 

          

 

 

 

TEMPERATURE CONTROLLER FOR 3 WAY VALVE 

 

WITH OR WITHOUT  EXTERNAL TEMPERATURE COMPENSATION 

(IZOTHERMAL REGULATOR ) 3WM+A 

 

 
DESCRIPTION

 

 

The unit is applicable for controlling the output temperature of electrically actuated 3 way 
mixing valve: 
- Mode 1“Setp C =ExtTemp” – compensation of regulated temperature according to external 
temperature (isothermal regulation)  
- Mode 2“ Setp C =Local T” – fixed temperature preset by user 
 

 
 
 
 
 
 
 
 
 

Characteristics: 
1.

 

Control commands for „Open” and „Close” for directions of motor driven 3-way mixing 

valve. 
2.

 

Reads 1 or 2 temperatures 

3.

 

Parameters 16  

4.

 

User selectable mode of operation – fixed temperature or isothermal regulator 

5.

 

Push button Start/Stop 

6.

 

Power supply  – 230 V AC, consumption  <2VA 

7.

 

Outputs: 2 x – separate relays for commutation of : 

-

 

R1 n.o.  – for “open” command  

-

 

R2 n.o.  – for “close” command 

8.

 

LCD display – alphanumeric 8х2  

9.

 

Buttons for navigation – 3pcs. 1 Button for On/Off 

 

TECHNICAL DATA

 

 

Power Supply:     230V±10% /50Hz. ≤ 2VА
 

 

Installation  on  DIN  rail  35mm;    for 
incorporation  

Operating temperature: -5T40, RH80% 
Transport                      -20/+60 º C

 

Overall dimensions:  68x85x58 mm. 
Case    IP20 

Sensor types:   PTC 1k 
Reading range :  -40ºC÷150 ºC;  
Accuracy ±1ºC if (-5ºC ÷ +100 ºC); else±4ºC. 

Outputs:  
-Relay R1- 230V  -   5A  и  180W/AC3 (motor)     
-Relay R2- 230V  -   5А  и 1500W/AC3(motor) 
-Relay R3- 230V  -   5A  option

 

-

 

Power supply  230V AC                  – (internal and R1) – #17 (Live “La”);  #16 („N”); 

-

 

R1: valve – “open”     

                 – #18 (switches Live); #15 („N”);       –   5А max. 

-

 

R2: valve – “close”   

 

       – #20 (separate Live ”Lb”); #22 output  – 5А max. 

-

 

R3: Option

 

 

---------- PROXEL ENGINEERING ---------------- www.proxel-bg.com-------------------------------- 3WMREG rev. 2.4 /02.2017------      
 

 

          

 

 

WIRING DIAGRAM 

 

 

 

Instalation and commusioning 
 
 
 
 

 
This device is dedicated to be incorporated in apartment electrical box with size of 4 or more poles 
or a cabinet and can be attached on 35mm DIN rail. 
 
 
 
 
 
 
 
 

Sensors and outputs wiring:

 

 

1. Scheme 1 “Local Setp” (Regulates output temperature to a fixed set point)

 

TS1

: Regulated temperature

 

TS2

:not used

 

TS3

: Room temperature

 

R1:

 “Open” direction

 

R2

: “Close” direction

 

2. Scheme 2 “TSyphReC” (Regulates output temperature to a variable set point, ambient 
temperature dependant)

 

TS1

: Regulated temperature

 

TS2

: Ambient temperature

 

TS3

: Room temperature

 

R1:

 отваряне

 

R2

: затваряне

 

 

 
PARAMETERS: 
„ROOM T.”     – Set point of room temperature. 

[range = 10º C ÷ 45º C]. Factory= 25 º C;

  

1.

 

„Set T.”       – Set point of water temperature.   

[range = -10º C ÷ 90º C]. Factory = 40 º C; 

 

2.

 

„±Hist I”    – Hysteresis  1 (fine regulation) 

[range 2º C ÷ 10º C] Factory= +5º C 

 

3.

 

„±Hist II”  – Hysteresis 2   (coarse regulation)  

[range Hist I +2º C ÷ Hist I+ 15º C] Factory = +15 º C

 

4.

 

„PulseDur” – Duration of signal pulses for “moving” the valve - either direction.

 

[range  0. 5sec ÷5.0 sec] Factory = + 1.0 sec; 

 

5.

 

„ON<>OFF”   – Time constant of valve to change from fully open to fully close state. 

 

[range 15 sec  ÷ 250 sec] Factory . = 60  sec;

 

6.

 

„”  – Period of applying signal pulse for direction “open”

 

[range 5 sec ÷ 60 sec] Factory = 15 sec”

 

7.

 

„Period-”  – Period of applying signal pulse for direction “close”

 

[range 5 sec ÷ 60 sec] Factory = 15 sec”

 

8.

 

„Setp=”  – Mode of operation : at fixed set point (local) or with temperature compensation 
based on ambient temperature 

9.

 

“dTAlarm”  – Alarm temperature ,a ± margin from current set point. If temperature reading is 
“outside” this margin device starts emergency “open” or “close” procedure

 [-35

º C ÷ 35º C].  

Factory = 35

 

Attention! 

3WMreg is not a safety device as by means of

 

EN60730-1-Annex H

  

 

 

Attention!                           

Danger of electric shock! 

   All activities involving installation and commissioning should be done while electric power is off

 

Attention!        
 Power supply should be applied via fuses Phase-La / Lb  6A max. 

 