7.2.2.3 IEC 60870-5-101/104
– -104 slave
Settings -
104 slave
:
Parameter
Description
Range
Factory value
Unit
APDU timeout (t1)
Time limit for sent unconfirmed message.
If the time has expired, communication is closed.
1..3600
15
s
ACKN timeout (t2)
Deadline for received unconfirmed messages.
Confirmation (ackn) is sent no later than this time.
1..3600
10
s
TEST timeout (t3)
Test message timeout. Test message is sent no
later than this time.
1..3600
30
s
k unackn I format
ASDU
Maximum number of unconfirmed messages (I
format). If exceeded, communication is closed.
1..255
12
-
w ackn I format ASDU
Maximum number of unconfirmed received
messages (I format). Confirmation (ackn) will be
sent no later than this number.
1..255
8
-
Command timetag
timeout
Maximum difference between local time in the unit
and time marking on an order. If the telegram
does not arrive in time, the order is not allowed.
1..3600
30
s
Time tag type
Specifies the type of time format IPC402x uses.
-
1
CP56
-
Common address
(CA) size
Size of the RTU address, number of octets.
-
1
2
octet
Object address
(OA) size
Size of the object address, number of octets.
-
1
3
octet
Cause of transmission
(COT) size
Size of
”COT”, number of octets.
-
1
2
octet
7.2.3 IEC 60870-5-101 master - OPTIONAL
IPC4020 can be obtained with the option
IEC -101-master for IPC402x
. With this option, IPC4020 can act
local IEC-101 master, which enables the user to connect an additional number of local -101 slaves.
The settings are found on the
Communication/IEC 60870-5-101/104/-101 master
tab.
1
This is for information only and cannot be changed by the user.