Table 5-1 RDSP Runtime warning messages
W
ARNING MESSAGE
(RDSP
R
UNTIME
)
E
XPLANATION
0x0001 (noPSAD)
PS modules with auxiliary voltage measurement do not
transmit the measured value to the CPU properly.
Suspected HW error.
0x0002 (vlanMismatch)
In line protection and binary signal exchange
applications the VLAN settings are inconsistent.
Consistency check recommended.
0x0004 extRtcCalibMode
CPU Real Time Clock accuracy is out of the tolerance
range. Internal device clock
won’t work accurately, while
the device is switched off. Suspected HW error.
0x0010 psVoltUnstab
The device internal power supply voltage (+/-12V) is
unstable on the CT/VT module. Possible power supply or
backplane failure.
0x0400 siliconRevMismatch
The RDSP firmware and the CPU chip hardware
versions are different.
0x8000 adControlWarn
AD converter failure on an analogue input module. The
faulty module can be determined from the RDSP log,
which can be opened in the advanced menu status/log
submenu LOG files field. Suspected HW error.
Table 5-2 CDSP warning messages
W
ARNING MESSAGE
(CDSP)
E
XPLANATION
0x0001 (System)
System level warning (e.g.: Parallel DRL message
version discrepancy)
0x0002 (Config)
Configuration inconsistency or structural problem. The
system is still operating.
0x0004 (Param)
Parameter problem, such as:
-
during startup the device is unable to determine the
number of parameter sets
-
parallel DRL addressing warning (same master and
slave address used)
0x0008 (LCD application)
System level warning, which is hampering LCD startup.
It may happen when the device is building up
communication between the RDSP and the CDSP via
the high-speed bus application (sport).
0x0040 (Time synchronization)
Time synchronization warning. Check the Time synch.
settings in the system settings menu and verify the
signal source.
0x0100 (RDSP comm. error)
RDSP communication problem. Software inconsistency
or hardware error possible.