PAGE 24
PROGRAM CODES
I/O Configuration
After you enter Program Code 5, the B1290 prompt for the Configuration Code. If you wish to go back to the
Enter
Program Code
prompt without going through all of the codes, enter
.
B1290: "Enter Configuration Code"
YOU:
Alarm Input Setup
Using Directory
Relay Setup
Exit to Enter Program Code prompt
Alarm Input Setup
Alarm Format
This parameter changes the format of the B1290 alarm inputs to match the output of your monitoring devices in
the field. Normally open inputs indicate an alarm when the input is grounded, and when the ground signal is
removed, the alarm is interpreted as having cleared. Normally closed inputs are grounded in their normal state,
and open when an alarm occurs. Latched inputs recognize a pulse as an
alarm. After the pulse has disappeared,
the input is deemed to be in the alarm condition until it is acknowledged.
Note
: A latched alarm should provide a short, predictable pulse to the input of the ProTalk Plus; otherwise, it
may have to be acknowledged twice. If the alarm is acknowledged while the input is active, the alarm will not
be cleared and new alarms will not activate that input.
B1290:
"Alarm Format is …"
YOU:
Normally Open
Normally Closed
Normally Open, Latched
Normally Closed, Latched
Next
Default:
0 (normally open)
Alarm Timer (Debounce) Timescale
The debounce timers on the alarm inputs can operate with a resolution of .1 seconds or .1 minutes. When the
B1290 speaks ‘seconds’ for this value it is indicating that the timer is counting in .1 second steps and when it
speaks ‘minutes’ it is counting in .1 minute steps.
B1290:
"Alarm Timer is seconds"
YOU:
Seconds
Minutes
Next
Default:
0 ( seconds)
Alarm Delay (Debounce)
This parameter controls the amount of time an alarm must be present before it actually registers as an alarm.
This feature is often used to eliminate fleeting alarms, where the device in the field does not present a clean
closure to indicate an alarm, but a series of bounces on the contacts. Another example might be to overcome
momentary power fluctuations which cause false alarms to be reported. The debounce on each alarm may be
individually set.
B1290:
"Alarm One Delay is _ _ point _ seconds"
YOU:
( x = 0.1 to 19.9 )
Summary of Contents for Plus B1290
Page 1: ...Installation Operation Manual January 2022 Rev 2 04 ...
Page 4: ......
Page 19: ...OPERATION PAGE 15 ...
Page 49: ...PROGRAMMING EXAMPLES PAGE 45 etc ...
Page 60: ...PAGE 56 APPENDIX C PROGRAMMMING TREE Next ...
Page 61: ...APPENDIX D MOUNTING PAGE 57 15 APPENDIX D MOUNTING Figure 9 Mounting Detail ...