Reference
MVI56E-MNETCR ♦ ControlLogix Platform
User Manual
Modbus TCP/IP Multi-Client Enhanced Communications Module for Remote Chassis
Page 104 of 161
ProSoft Technology, Inc.
5.1
Product Specifications
The MVI56E Modbus TCP/IP Multi-Client Enhanced Communications Module for
Remote Chassis allows Rockwell Automation
®
ControlLogix
®
Programmable
Automation Controllers (PACs) to interface easily with multiple Modbus TCP/IP
server-compatible instruments and devices. The multi-Client module improves
performance when controlling multiple servers on a Modbus TCP/IP network, by
supporting up to 30 Clients.
MVI56E enhancements include configuration and management through the
module’s Ethernet port, and CIPconnect
®
technology for bridging though
ControlNet™ and EtherNet/IP™ networks.
This module uses a small I/O data image for transfer of data between the module
and the ControlLogix processor, making it ideal for ControlNet or Ethernet
applications with the module in a remote rack.
5.1.1 General Specifications
Backward compatible with previous MVI56-MNETCR versions
Single-slot 1756 ControlLogix backplane compatible
10/100 Mbps auto crossover detection Ethernet configuration and application
port
User-definable module data memory mapping of up to 5000 16-bit registers
CIPconnect-enabled network configuration and diagnostics monitoring using
ControlLogix 1756-ENxT and 1756-CNB modules
ProSoft Configuration Builder (PCB) software supported, a Windows-based
graphical user interface providing simple product and network configuration
Sample ladder logic and Add-On Instructions (AOI) are used for data transfer
between module and processor
4-character, alpha-numeric, scrolling LED display of status and diagnostics
data in plain English
– no cryptic error or alarm codes to decipher
ProSoft Discovery Service (PDS) software used to locate the module on the
network and assign temporary IP address
Personality Module - a non-volatile industrial-grade Compact Flash (CF) card
used to store network and module configuration for easy disaster recovery,
allowing quick in-the-field product replacement by transferring the CF card
Modbus TCP/IP Client (Master)
The MVI56E-MNETCR is a Client-only module that will operate on a local or
remote rack. This module was created to improve performance when controlling
multiple servers on a Modbus TCP/IP network.
Offers 30 Client connections with up to 16 commands each to talk to multiple
servers
Actively reads data from and writes data to Modbus TCP/IP devices, using
MBAP or Encapsulated Modbus message formats
Transmits Modbus Function Codes 1, 2, 3, 4, 5, 6, 7, 15, and 16
Summary of Contents for MVI56E-MNETCR
Page 4: ......