Configuring the MVI56E-MCMR Module
MVI56E-MCMR ♦ ControlLogix Platform
User Manual
Modbus Communication Module with Reduced Data Block
Page 94 of 223
ProSoft Technology, Inc.
2.7.1 Using CIPconnect
®
to Connect to the Module
You can use CIPconnect
®
to connect a PC to the ProSoft Technology MVI56E-
MCMR module ove
r Ethernet using Rockwell Automation’s 1756-ENBT
EtherNet/IP
®
module. This allows you to configure the MVI56E-MCMR network
settings and view module diagnostics from a PC. RSLinx is not required when
you use CIPconnect. All you need are:
The IP addresses and slot numbers of any 1756-ENBT modules in the path
The slot number of the MVI56E-MCMR in the destination ControlLogix
chassis (the last ENBTx and chassis in the path).
To use CIPconnect, follow these steps.
1
In the
Select Port
dropdown list, choose
1756-ENBT
. The default path
appears in the text box, as shown in the following illustration.