ILX56-PBS
Technical Specifications
ControlLogix® Platform
User Manual
Page 64 of 87
6. Technical Specifications
Electrical
Specification
Rating
Backplane Current Load
450 mA @ 5 VDC
2 mA @ 24 VDC
Enclosure rating
IP20, NEMA/UL Open Type
Temperature
-20 to 70 °C
Earth connection
Yes, terminal based
Emissions
IEC61000-6-4
ESD Immunity
EN 61000-4-2
Radiated RF Immunity
IEC 61000-4-3
EFT/B Immunity
EFT: IEC 61000-4-4
Surge Immunity
Surge: IEC 61000-4-5
Conducted RF Immunity
IEC 61000-4-6
Table 6.1 - Electrical specification
PROFIBUS DP
Specification
Rating
Connector
Female DB9 connector
Conductor
See
PROFIBUS DP
Section.
DP Master Mode Support
DPV0 Data Exchange
DPV1 Class 1 Messaging
DPV1 Class 2 Messaging
DPV1 Alarming
DP Slave Mode Support
DPV0 Data Exchange
DPV1 Class 1 Messaging
DPV1 Alarming
Isolated
Yes
BAUD Rate supported
9.6 kbps, 19.2 kbps, 45.45 kbps, 93.75 kbps, 187.5 kbps, 500 kbps, 1.5 Mbps,
3 Mbps, 6 Mbps, 12 Mbps,
Table 6.2
– PROFIBUS DP specification
Certifications
Please visit our website: www.prosoft-technology.com