Setup
Page 41 of 69
3.7.2.
RSL
OGIX
5000
C
ONFIGURATION
(P
RE
-V
ERSION
20)
3.7.2.1.
ADD MODULE TO I/O CONFIGURATION
The module can operate in both a Logix “owned” and standalone mode. When the module
operates in “owned” mode, the PLX51-DF1-ENI needs to be added to the RSLogix 5000 IO tree
as a generic Ethernet module. This is done by right clicking on the Ethernet Bridge in the
RSLogix 5000 and selecting New Module. Select the ETHERNET-MODULE as shown in the
figure below.
NOTE: See the next section for importing the configuration (L5X).
Figure 3.41 - Add a Generic Ethernet Module in RSLogix 5000
In the Module Properties dialog, enter the IP address, the assembly instance, and size for the
input, output, and configuration. Below are the required connection parameters.
Connection Parameter
Assembly Instance
Size
Input
100
34 (32-bit)
Output
101
1 (32-bit)
Configuration
102
0 (8-bit)
Table 3.3 - RSLogix class 1 connection parameters for the PLX51-DF1-MSG