Setup
Page 31 of 69
3.5.2.
S
CHEDULED
T
AG
M
ODE
The Scheduled Tag routing mode transfers data between a DF1 device and one or more Logix
controllers (the PLX51-DF1-MSG initiates the messaging when in the Scheduled Tag mode).
In this mode, the PLX51-DF1-MSG transfers data between a Logix controller and a DF1 device
without any configuration or programming required in either the DF1 device or the Logix
controller.
Figure 3.24 - Scheduled Tag configuration
The Schedule Tag mode is configured in three steps. First, you must create a Target Name (CIP
path to the destination Logix controller) which will be used to link the DF1 File Number to the
destination Logix tag.
The Logix controller paths can either be entered manually or you can browse to them by
clicking the Browse button. The Target Browser opens and automatically scans for all available
EtherNet/IP devices.