EIP Protocol
PLX3x Series ♦ Multi-Protocol Gateways
User Manual
Page 76 of 215
ProSoft Technology, Inc.
January 25, 2018
Forward Open Response Error Codes
Error (Int)
Error (Hex) Description
-55
0xFFC9
Message length received not valid
-56
0xFFC8
Status error reported
PCCC Response Error Codes
Error (Int)
Error (Hex) Description
-61
0xFFC3
Message length received not valid
-62
0xFFC2
Status error reported
-63
0xFFC1
CPF bad command code
-64
0xFFC0
TNS in PCCC message not matched
-65
0xFFBF
Vendor ID in PCCC message not matched
-66
0xFFBE
Serial number in PCCC message not matched
5.4
EIP Reference
5.4.1 SLC and MicroLogix Specifics
Messaging from a SLC 5/05
The PLX3x gateway can receive messages from a SLC 5/05 containing an
Ethernet interface. The gateway supports both read and write commands.
SLC5/05 Write Commands
Write commands transfer data from the SLC processor to the gateway. The
following diagram shows an example rung to execute a write command.
1
Set the
R
EAD
/W
RITE
parameter to
W
RITE
.
The gateway supports a
T
ARGET
D
EVICE
parameter value of
500CPU
or
PLC5
.