Reference MVI56-BDW
♦
ControlLogix Platform
BARDAC Drive Web Interface
ProSoft Technology, Inc.
Page 67 of 82
September 4, 2008
Code Description
3
Illegal data value
6
Busy, reject
7
Negative acknowledge
10
Read-only variable
11
Index out of range
12
Invalid data type
13
Invalid variable address
14
Invalid modbus address
15
Connection not setup
16
Write-only variable
17
EEPROM write fail
0xFFFD
Device not ready (initializing)
0xFFFE
Device lock timeout (serious problem with device)
0xFFFF
Unable to obtain device lock (device servicing other transaction)
Others
Refer to drive manual or contact Bardac.
UDP Error Codes
Code Description
0xFFDF
Could not find IP on network
0xFFDE
Buffer for UDP socket could not be allocated
0xFFDC
Command response timeout
Command List Entry Errors
Code Description
40
Too few parameters for command
41
Invalid type code
42
Invalid internal database address
45
Invalid function code
46
Invalid swap code
5.3 Cable
Connections
The MVI56-BDW module has the following communication connections on the
module:
One Ethernet port (RJ45 connector)
One RS-232 Configuration/Debug port (RJ45 connector)
5.3.1 Ethernet
Connection
The MVI56-BDW module has an RJ45 port located on the front of the module
labeled "Ethernet", for use with the TCP/IP network. The module is connected to
the Ethernet network using an Ethernet cable between the module's Ethernet
port and an Ethernet switch or hub.