Configure the Adapter for Master/Slave Communication
3170-PDP
♦
FLEX Platform
FLEX I/O™ PROFIBUS Adapter
ProSoft Technology, Inc.
Page 61 of 152
August 23, 2007
5.4
Configuration Example Using PROFIBUS Manager Software
For more detailed information on configuring your network, refer to your
PROFIBUS Manager User Manual, publication 1785-6.5.20.
If you are using another configuration tool, how you access and enter data is
similar, however, refer to the user documentation supplied with that tool.
The directions in this example assume you have the software installed and have
constructed a DP network containing at least one 3170-PDP FLEX I/O
PROFIBUS adapter module.
User Parameter Example
User Parameter Message, Full Format
Name Value
Description
Octet 8:
00h
Reserved
Octet 9:
OBh
Full Format, Use safe state
Octet 10 to 11:
0281h
Slot 1 Module Key 1794-IB16 16-point discrete input module
Octet 12:
10h
Slot 1 config size 1 word, safe state size 0 words
Octet 13 to 14:
0000h
1 config word, input delay times
Octet 15 to 16:
0191h
Slot 2 Module Key 1794-OB16 16-point discrete output module
Octet 17:
01h
Slot 2 config size 0 words, safe state size 1 word
Octet 18 to 19:
0000h
1 safe state data word, safe state value for output points
Octet 20 to 21:
1920h
Slot 3 Module Key 1794-IE8 8-point analog input module
Octet 22:
10h
Slot 3 config size 1 word, safe state size 0 words
Octet 23 to 24:
0000h
1 config word, channel selection
Octet 25 to 26:
5121h
Slot 4 Module Key 1794-OE4 4-point analog output module
Octet 27:
24h
Slot 4 config size 2 words, safe state size 4 words
Octet 28 to 29:
0000h
4 safe state data words – safe state value for output point 1
output point 2
output point 3
output point 4
Octet 30 to 31:
0000h
Octet 32 to 33:
0000h
Octet 34 to 35:
0000h
Octet 36 to 37:
0000h
2 config words – channel selection and
output enable
Octet 38 to 39:
0000h
Octet 40 to 41:
0FFFFh
Slot 5 empty
Octet 42:
00h
Slot 5 all sizes zero
Octet 43 to 44:
0FFFFh
Slot 6 empty
Octet 45:
00h
Slot 6 all sizes zero
Octet 46 to 47:
0FFFFh
Slot 7 empty
Octet 48:
00h
Slot 7 all sizes zero
Octet 49 to 50:
0FFFFh
Slot 8 Empty