ProMix Series S&C User Manual
2.9 Scale the 4-20mA Input
Press
ENTER
@
4-20 mA Input
to navigate the input current loop sub-menu
See the previous page for calibrating the 4-20 mA input loop
Press
DOWN
to view the present 4 mA pump feed
percentage.
The factory default is as displayed. When the 4-20 mA input
is at 4.0 mA the pump will be OFF.
Press
DOWN
to view the present 20 mA pump feed
percentage.
The factory default is as displayed. When the 4-20 mA input
is at 20.0 mA the pump will be 100%.
Press
DOWN
to view the response when the input current
loop is less than 4.0 mA.
The factory default is as displayed. When the 4-20 mA input
is less than 4.0 mA the pump will be OFF.
Press
ENTER
at any of the four sub-menu displays to
modify the present setting.
Press
EXIT
to leave unchanged.
Sidebar:
Calibration
of the 4-20 mA input ensures that the measured value of the 4-20 mA Input is
displayed as the correct mA level.
Scaling
the 4-20 mA input is required when you do not want 4-20 mA to correspond to a 0-
100% polymer feed rate.
Selecting a different response than Pump OFF on loss of the 4-20 mA input allows for a wider
range of site operational configurations & control loop reliability.
Summary of Contents for ProMix C
Page 50: ...ProMinent ProMix S C Polymer Feeder ProMix Series S C User Manual B 2 Control Panel Drawings...
Page 51: ...ProMinent ProMix S C Polymer Feeder ProMix Series S C User Manual...
Page 52: ...ProMinent ProMix S C Polymer Feeder ProMix Series S C User Manual...
Page 53: ...ProMinent ProMix S C Polymer Feeder ProMix Series S C User Manual...
Page 54: ...ProMinent ProMix S C Polymer Feeder ProMix Series S C User Manual...
Page 55: ...ProMinent ProMix S C Polymer Feeder ProMix Series S C User Manual...