20
Technical data and operating parameters
Application
Type
Sample water
Operating pressure
Potable water (P) C0, C1, D0, I0, Z0, F0, H0, X0
1
1 bar at 45 °C
Potable water (P) G0, A0
1
3 bar at 45 °C
Potable water (P) C1, D0, I0, Z0, F0, H0, X0
2
1 bar at 45 °C
Potable water (P) C1, P0, R0, L0
H
2 bar at 65 °C
Waste water (W)
C1, D0, I0, Z0, F0, H0, X0
4, 5, 7
1 bar at 45 °C
Waste water (W)
G0, A0
2, 4, 5, 7
3 bar at 45 °C
Waste water (W)
C1, P0, R0, L0
H
2 bar at 65 °C
Sample water
Designation
Definition
1
Drinking water.
Drinking water in accordance with the
German Drinking Water Ordinance.
2
Rinsing water.
Process water with a low purity level (with
small particles of dirt, turbid appearance).
Industrial water.
Process water.
4
Clear waste water.
Waste water with a low purity level (with
small particles of dirt and chemical pollu‐
tion).
5
Waste water with solid particle frac‐
tion, turbid.
Waste water with a low purity level (with
particles of dirt < 1 mm, floating bodies,
turbid and chemical pollution).
7
Waste water with fluoride and pH <
7.
Waste water with a low purity level (with
small particles of dirt, turbid appearance).
H
Potable water, rinsing water, indus‐
trial water, process water, clear
waste water, waste water with solids
content, for higher temperatures.
Temperature max. 65 °C at max. pressure
of 2 bar.
Refer to the specifications for the series components.
Refer to the specifications for the series components. The pipe‐
work in the bypass consists of glued PVC fittings.
The electrical components have a wide-voltage power unit and can
be operated at 100 ... 230 VAC 50/60 Hz.
Electrical connection:
n
100 ... 230 V 50/60 Hz
n
0.7 ... 0.3 A
n
35 W
Permissible operating pressures
Definition of "sample water"
Precision
Material specifications/Manufacturing
processes/Chemical resistance
Electrical data
Technical data and operating parameters
126