4
Assembly and electrical installation
Please follow this order:
A. - Install the housing
B. - Install the PROFIBUS
®
cable
C. - Connect DULCOnvert to the mains voltage
D. - Install the PROFINET
®
cable
E. - Properly close the housing
1.
Flap open the two flaps on the left and right of the housing
cover.
2.
Use appropriate screws to screw the housing to a vertical
base surface close to the pump using the 4 deep drill holes
(taking into account the length of the PROFIBUS
®
cable and
the plug-in power unit).
CAUTION!
When installed, the top should be pointing
upwards otherwise the specific IP degree of
protection will not be achieved.
Connect the PROFIBUS
®
cable from the DULCOnvert to the
pump’s PROFIBUS
®
socket.
There is no need for terminal resistors.
Connect the plug-in power unit of the DULCOnvert to the
mains voltage.
1.
Unscrew the housing screws and open the cover.
2.
Screw the clamping screw of the large threaded connector on
the left of the housing and remove the rubber insert.
3.
Correctly thread the clamping screw the right way round onto
your PROFINET
®
cable.
4.
Guide the PROFINET
®
cable into the housing and insert it
into the socket on the converter until it snaps into place.
5.
Place the rubber insert around the cable and press into the
threaded connector.
6.
Screw the clamping screw onto the threaded connector until
it is moisture-tight.
A. Installing the housing
B. Installing the PROFIBUS
®
cable
C. Connecting the DULCOnvert to the
mains voltage
D. Installing the PROFINET
®
cable
Assembly and electrical installation
9